Unichiller 022w Datasheet

Contents

  1. Overview p. 1
    Introduces the Unichiller 022w chiller and its main features
  2. Spec pp. 1-2
    Lists performance, temperature, and physical specifications per DIN 12876
  3. p. 2 table, 6 rows
  4. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
max. current6,5 A
Fuse16 A
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S580475

Technical data according to DIN 12876

ParameterValue
Operating temperature range-10...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at ambient temperature +20°C at 15°C2,2 kW
at 0°C1,6 kW
at -10°C1 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-290 (A3, H220)
Global Warming Potential (GWP)0,02
Refrigerant quantity0,17 kg
CO2 equivalent0,0 t
UN-numberUN 3358
Circulation pumpImmersion pump
max. delivery29 l/min
max. delivery pressure1 bar
Delivery at 0,5 bar21 l/min
Pump connectionG3/4 male
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 15°C95 l/h
Consumption at water 15°C, flow 0°C96 l/h
Consumption at water 15°C, flow -10°C77 l/h
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity3,8 l
Volume of expansion1,7 l
Overall dimensions WxDxH **420x487x579 mm
Net weight61 kg
sound pressure level +/- 4 dB(A)60 dB(A)
Power supply requirement220-240V 1~ 50Hz

** Overall dimensions WxDxH

Engineering Facts

13 facts · every claim linked to a page
Installation

The chiller requires cooling water inlet temperature between 5°C and 20°C, so the facility water supply must be capable of maintaining that range.

Determines whether the site cooling water supply is suitable and whether additional chilling or mixing is needed.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

If cooling water temperature can fall below the condensation point, the cooling water pipes inside the unit must be insulated.

Prevents condensation and corrosion/electrical risk when cold cooling water is used.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Cooling capacity drops and cooling water flow rate may need to increase as the cooling water temperature rises.

Affects sizing of the cooling water supply and expected process performance at higher facility water temperatures.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so the cooling water must be compatible with these materials.

Guides water quality and treatment requirements to avoid corrosion or deposits.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Operation

The plastic pump is not resistant to acetone or polyglycols, so these fluids must not be used as the heat transfer medium.

Prevents chemical attack and pump failure when selecting the heat transfer fluid.

Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation

For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.

Ensures safe operation at sub-zero temperatures and avoids freezing damage.

Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Compliance

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.

Defines acceptable power supply quality and prevents invalid supply combinations during site assessment.

Source
“-5% voltage and +2% frequency -> not allowed!”
Compliance

The unit is classified as EN55011 Class A, Group 1 for electromagnetic disturbance, which has implications for the installation environment.

Class A equipment may require additional EMC measures in residential or sensitive environments.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

Single/two-phase devices are supplied with a power cable and country-specific plug, which must be specified at ordering.

Ensures the correct plug type is delivered and avoids delays or rework at installation.

Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”
Selection

The unit is compliant with US-SNAP and applicable EU laws, with US-SNAP end-use defined as industrial process refrigeration.

Confirms regulatory suitability for industrial process refrigeration applications in the US and EU.

Source
“This equipment is compliant to US-SNAP and all applicable EU laws. The US-SNAP end-use for this equipment is the industrial process refrigeration.”
Installation

Space requirements around the unit must be respected according to the operating conditions published online.

Prevents installation in insufficient space that could affect performance or service access.

Source
“Please respect space requirements. See operating conditions at www.huber-online.com”
Operation

The Pilot ONE controller supports USB and network connections, enabling remote control and data transmission with Spy software.

Useful for integration into monitoring or data logging systems.

Source
“The USB port allows connection of the system to a PC or notebook. Together with the Spy software, requirements such as remote control or data transmission are easily achieved in a cost-effective manner.”
Selection

The unit uses R-290 refrigerant with GWP 0.02 and a charge of 0.17 kg, which is relevant for environmental and safety assessments.

R-290 is flammable (A3), so safety measures and refrigerant regulations must be considered.

Source
“Refrigerant (ASHRAE, GHS) R-290 (A3, H220)”