The chiller requires a three-phase 400 V supply with a 3x16 A fuse, so the site must provide a suitable three-phase feed.
Determines electrical infrastructure and breaker sizing before installation.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
| Parameter | Value |
|---|---|
| Power supply (3 Phase) | 400V 3~ 50Hz |
| max. current (3 Phase) | 14 A |
| Fuse (3 phase) | 3x16A |
| Pressure equipment category | Art. 4.3 PED |
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
| max. ambient temperature | 40 °C |
| from Serial-No.: | S610745 |
| Parameter | Value |
|---|---|
| Operating temperature range | -20...100 °C |
| temperature set point / display | 5,7" colour Touchscreen |
| Internal temperature sensor | Pt100 |
| Sensor external connection | Pt100 |
| Interface digital | Ethernet, USB (Host u. Device), RS232 |
| Temperature stability at -10°C | 0,2 K |
| Safety classification | III / FL |
| Heating power | 2 kW |
| Cooling power at 15°C | 6 kW |
| Cooling power at 0°C | 5 kW |
| Cooling power at -10°C | 2,8 kW |
| Cooling power at -20°C | 1,4 kW |
| Refrigeration machine | air-cooled, CFC- and HCFC-free |
| Refrigerant (ASHRAE, GHS) | R-449A (A1, H280) |
| Global Warming Potential (GWP) | 1397 |
| Refrigerant quantity | 2,2 kg |
| CO2 equivalent | 3,1 t |
| Circulation pump: | C3 |
| max. delivery | 80 l/min |
| max. delivery pressure | 5,6 bar |
| Delivery at 0,35 bar | 79 l/min |
| Delivery at 0,5 bar | 76 l/min |
| Delivery at 1,0 bar | 71 l/min |
| Delivery at 1,5 bar | 66 l/min |
| Delivery at 2,0 bar | 61 l/min |
| Delivery at 3,0 bar | 49 l/min |
| Delivery at 4,0 bar | 35 l/min |
| Delivery at 5,0 bar | 16 l/min |
| Pump connection | G1 1/4 male |
| min. filling capacity | 5 l |
| Volume of expansion | 7,5 l |
| Overall dimensions WxDxH ** | 600x692x1613 mm |
| Net weight | 235 kg |
** см. сноску в оригинале (Overall dimensions WxDxH **)
The chiller requires a three-phase 400 V supply with a 3x16 A fuse, so the site must provide a suitable three-phase feed.
Determines electrical infrastructure and breaker sizing before installation.
“Power supply (3 Phase) 400V 3~ 50Hz”
Three-phase devices under 63 A are delivered with a cable but without a plug, so the customer must supply and fit the plug.
Affects electrical installation scope and ordering of mating plug.
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Voltage and frequency tolerances must be met simultaneously, and a -5% voltage with +2% frequency combination is not allowed.
Prevents connecting to a supply whose combined tolerances could damage the unit.
“-5% voltage and +2% frequency -> not allowed!”
Cooling capacity is rated at 20 °C room temperature and may drop if ambient temperature rises.
Needs to be considered when sizing cooling capacity for the actual site ambient.
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
The unit must be operated within an ambient temperature range of 5 °C to 40 °C.
Defines allowable installation environment and ventilation requirements.
“min. ambient temperature 5 °C”
The refrigerant R-449A is classified A1 with GHS hazard H280, so refrigerant handling and leak precautions apply.
Informs safety measures and labeling for refrigerant handling.
“R-449A (A1, H280)”
The unit has a CO2 equivalent of 3.1 t based on 2.2 kg of R-449A with GWP 1397, which matters for F-gas reporting.
Required for refrigerant leak checks and environmental compliance records.
“CO2 equivalent 3,1 t”
The pump connection is G1 1/4 male, so mating hoses and couplings must match this thread.
Ensures correct hydraulic connection and avoids adapters or leaks.
“Pump connection G1 1/4 male”
The minimum filling capacity is 5 l and expansion volume is 7.5 l, which sets the minimum system volume and expansion allowance.
Prevents undersized external loops and ensures expansion tank capacity is adequate.
“min. filling capacity 5 l”
The unit is air-cooled and requires respect of space requirements per operating conditions.
Air-cooled units need sufficient clearance for heat rejection and service access.
“Please respect space requirements. See operating conditions at www.huber-online.com”
The equipment is EMC Class A Group 1, which may require additional filtering in residential or sensitive environments.
Class A equipment is intended for industrial environments and may cause interference elsewhere.
“Classification (disturbance) to EN55011: Class A, Group 1”
The unit has adjustable overtemperature protection according to DIN 12876, which must be set for the application.
Critical safety setting to prevent overheating of the bath or external process.
“With adjustable overtemperature protection according to DIN 12876.”
The circulation pump delivers 80 l/min max and 5.6 bar max pressure, with flow dropping as pressure rises.
Used to verify the pump can overcome external loop pressure drop at required flow.
“max. delivery 80 l/min”
The unit has a digital level indicator and atmospheric open expansion tank, so fluid level monitoring and venting are part of operation.
Supports routine checks of heat transfer fluid level and expansion tank condition.
“With digital level indicator.”