Introduces the Unichiller 075w-H chiller and its main features
Specpp. 1-2
Performance, temperature, and dimensional data per DIN 12876
p. 2table, 15 rows
p. 1table, 34 rows
Technical data according to DIN 12876
Parameter
Value
Consumption at water 15°C, flow -20°C
240 l/h
min. cooling water differential pressure
0,5 bar
max. cooling water pressure
6 bar
min. filling capacity
18 l
Volume of expansion
48 l
Overall dimensions WxDxH **
740x1160x1050 mm
Net weight
300 kg
Power supply (3 Phase)
400V 3~ 50Hz
max. current (3 Phase)
12,5 A
Fuse (3 phase)
3x16A
Pressure equipment category
Art. 4.3 PED
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S469065
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876 — Unichiller 075w-H (Order-No.: 3040.0010.01)
Parameter
Value
Operating temperature range
-20...100 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,2 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
III / FL
Heating power
2 kW
Cooling power at ambient temperature +20°C
at 100°C
7,5 kW
at 20°C
7,5 kW
at 0°C
6,1 kW
at -10°C
4 kW
at -20°C
2,4 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)
Global Warming Potential (GWP)
1397
Refrigerant quantity
0,95 kg
CO2 equivalent
1,3 t
Circulation pump
E1
max. delivery
48 l/min
max. delivery pressure
3,4 bar
Delivery at 0,3 bar
46 l/min
Delivery at 0,5 bar
44 l/min
Delivery at 1,0 bar
40 l/min
Delivery at 1,5 bar
33 l/min
Delivery at 2,0 bar
27 l/min
Delivery at 2,5 bar
20 l/min
Delivery at 3,0 bar
11 l/min
Pump connection
G1 1/4 male
Cooling water connection
G1/2 male
Consumption at water 15°C, flow 20°C
348 l/h
Consumption at water 15°C, flow 0°C
330 l/h
Consumption at water 15°C, flow -10°C
270 l/h
Строка «Cooling power at ambient temperature +20°C» является заголовком группы для последующих строк at 100°C / at 20°C / at 0°C / at -10°C / at -20°C; значение в её второй ячейке в исходном тексте отсутствует.
Engineering Facts
14 facts · every claim linked to a page
Installation
The chiller is water-cooled and requires cooling water supply between 5°C and 20°C, so the site must provide a suitable cooling water circuit.
Determines whether the facility's cooling water supply is compatible and whether additional chilling or insulation is needed.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water temperature falls below the condensation point, the cooling water pipes inside the unit must be insulated.
Prevents condensation and corrosion/electrical risk when using cold cooling water.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Cooling power drops and cooling water flow rate may increase as cooling water temperature rises, so performance must be derated accordingly.
Affects sizing and expected heat removal capacity at the actual site cooling water conditions.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and material compatibility to avoid corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Installation
Cooling water pressure must be between 0.5 bar minimum differential and 6 bar maximum.
Ensures adequate flow without overpressurizing the cooling water circuit.
Source
“min. cooling water differential pressure 0,5 bar max. cooling water pressure 6 bar”
Installation
The unit requires a 400V 3-phase 50Hz supply with max current 12.5 A and 3x16A fusing.
Determines electrical supply, cable and protection sizing for installation.
Source
“Power supply (3 Phase) 400V 3~ 50Hz max. current (3 Phase) 12,5 A Fuse (3 phase) 3x16A”
Installation
Three-phase devices with current consumption less than 63A are delivered with cable but without plug.
Installer must provide a suitable plug or hardwired connection.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Compliance
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Ensures the electrical supply quality is within the unit's allowed operating envelope.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety
The unit has adjustable overtemperature protection according to DIN 12876.
Important for safe operation and setting appropriate protection limits for the application.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Operation
The unit is intended for externally closed applications.
Confirms the hydraulic configuration and prevents misuse with open baths.
Source
“For externally closed applications.”
Operation
The refrigerant is R-449A with GWP 1397 and CO2 equivalent 1.3 t, which matters for environmental compliance and leak management.
Relevant for refrigerant handling, leak checks and environmental reporting.
Source
“Refrigerant (ASHRAE, GHS) R-449A (A1, H280) Global Warming Potential (GWP) 1397 Refrigerant quantity 0,95 kg CO2 equivalent 1,3 t”
Installation
The unit has IP20 protection and must be installed in an environment between 5°C and 40°C ambient temperature.
Defines environmental limits and protection against ingress for the installation location.
Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation
Overall dimensions are 740x1160x1050 mm and net weight is 300 kg, so space and floor loading must be planned.
Needed for site layout, access and structural considerations.
Source
“Overall dimensions WxDxH ** 740x1160x1050 mm Net weight 300 kg”
Compliance
The equipment is classified as EN55011 Class A Group 1 for electromagnetic disturbance.
Class A equipment may require EMC precautions in residential or sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”