Induztr
Engineering Digest Document Viewer Related Models

Unichiller 130Tw-H Technical Data Sheet

Contents

  1. Overview p. 1
    Product name and cover page for the chiller unit
  2. Spec p. 2
    Technical data table per DIN 12876 standard
  3. p. 2 table, 7 rows

Technical data according to DIN 12876

ParameterValue
max. current (3 Phase)12,5 A
Fuse (3 phase)3x16A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/21

Engineering Facts

12 facts · every claim linked to a page
Installation

The chiller is water-cooled and requires a cooling water supply with a minimum differential pressure of 1 bar and a maximum pressure of 6 bar.

To size the cooling water circuit and ensure the pump can deliver adequate flow without exceeding pressure limits.

Source
“min. cooling water differential pressure 1 bar max. cooling water pressure 6 bar”
Installation

The unit is designed for cooling water intake temperatures between 5°C and 20°C, and pipes must be insulated if condensation occurs.

To avoid condensation and ensure specified cooling performance; outside this range cooling power drops and flow requirements change.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C. When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Cooling power is rated at 13 kW at 15°C, 7 kW at 0°C, 4.5 kW at -10°C, and 4 kW at -20°C, valid for 20°C room and 15°C cooling water.

To select the chiller based on actual heat load at the required operating temperature, not just nominal capacity.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and - outlet.”
Installation

The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so the cooling water must be compatible.

To avoid corrosion or fouling that could reduce performance or damage the unit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Compliance

Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but combinations like -5% voltage and +2% frequency are not allowed.

To ensure the power supply quality meets the unit's requirements and avoid invalid operating conditions.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2% Example -5% voltage and +2% frequency -> not allowed! -5% voltage and - 2% frequency -> allowed”
Installation

Three-phase devices with current consumption less than 63A are supplied with a cable but without a plug.

To plan for a suitable plug and electrical connection on site.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety

The refrigerant R-449A has a GHS classification H280 (pressurized gas) and a GWP of 1397 with 2.5 t CO2 equivalent.

To assess safety measures for pressurized gas and environmental reporting obligations.

Source
“R-449A (A1, H280) Global Warming Potential (GWP) 1397 Refrigerant quantity 1,78 kg CO2 equivalent 2,5 t”
Operation

The minimum ambient temperature is 5°C and maximum is 40°C; operation outside this range is not permitted.

To ensure the installation location maintains acceptable ambient conditions for reliable operation.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The unit has a protection degree of IP20, so it must be installed in a dry, indoor environment protected from water ingress.

To avoid electrical hazards and equipment damage from dust or water.

Source
“Degree of Protection IP20”
Installation

The pump connections are G1 1/4 male and cooling water connections are G3/4 male, with hose couplings included.

To prepare matching fittings and hoses for installation.

Source
“Pump connection G1 1/4 male Cooling water connection G3/4 male”
Performance

The circulation pump delivers up to 96 l/min at a maximum pressure of 5.6 bar.

To verify the pump can overcome the pressure drop of the external circuit at the required flow rate.

Source
“max. delivery 96 l/min max. delivery pressure 5,6 bar”
Maintenance

The unit has a minimum filling capacity of 6.5 l and an expansion volume of 5.5 l, which must be considered when filling heat transfer fluid.

To ensure sufficient fluid volume and expansion space for safe operation.

Source
“min. filling capacity 6,5 l Volume of expansion 5,5 l”