Unichiller 180-H Datasheet

Contents

  1. Overview p. 1
    Introduces the Unichiller 180-H chiller and its main features
  2. Spec p. 2
    Technical data according to DIN 12876 standard
  3. p. 2 table, 9 rows
  4. p. 1 table, 34 rows

Technical data according to DIN 12876

ParameterValue
Net weight476 kg
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)14,5 A
Fuse (3 phase)3x16A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S590337

Technical data according to DIN 12876 — Unichiller 180-H (Order-No.: 3041.0018.01)

ParameterValue
Operating temperature range-20...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power2 kW
Cooling power at ambient temperature +20°C
at 100°C18 kW
at 20°C18 kW
at 0°C10 kW
at -10°C6 kW
at -20°C3,5 kW
Refrigeration machineair-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity1,7 kg
CO2 equivalent2,4 t
UN-numberUN 2857
Circulation pump:E1
max. delivery54 l/min
max. delivery pressure3,5 bar
Delivery at 0,3 bar52 l/min
Delivery at 0,5 bar48 l/min
Delivery at 1,0 bar42 l/min
Delivery at 1,5 bar36 l/min
Delivery at 2,0 bar28 l/min
Delivery at 2,5 bar21 l/min
Delivery at 3,0 bar11 l/min
Pump connectionG1 1/4 male
min. filling capacity18 l
Volume of expansion48 l
Overall dimensions WxDxH **938x1288x2003 mm

** см. сноску в оригинале (на странице не приведена).

Engineering Facts

14 facts · every claim linked to a page
Selection

The chiller is rated for an operating temperature range of -20 to 100 °C, so the process must stay within these limits.

Defines the application window and excludes processes outside this range.

Source
“Operating temperature range -20...100 °C”
Performance

Cooling capacity drops sharply at low temperatures (18 kW at 20 °C vs 3.5 kW at -20 °C), so size the unit for the coldest set point.

Prevents undersizing when the process requires low-temperature cooling.

Source
“at -20°C 3,5 kW”
Installation

The unit requires a 400 V three-phase supply with a 3x16 A fuse, so the electrical infrastructure must be prepared accordingly.

Determines the site power connection and protection device rating.

Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation

Three-phase devices below 63 A are delivered with cable but without a plug, so the customer must provide the plug.

Affects electrical installation planning and bill of materials.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Voltage and frequency tolerances are interdependent: -5% voltage with +2% frequency is not allowed, so the site supply must be checked.

Avoids invalid supply conditions that could damage the compressor or void warranty.

Source
“-5% voltage and +2% frequency -> not allowed!”
Operation

The unit is rated for ambient temperatures from 5 to 40 °C, and cooling capacity may drop above 20 °C.

Room conditions must be controlled to maintain rated performance.

Source
“If the ambient temperature rises, the cooling capacity may drop.”
Safety

The refrigerant is R-449A with GHS hazard H280 (pressurized gas), so handling and ventilation precautions apply.

Informs safety measures and refrigerant handling requirements.

Source
“R-449A (A1, H280)”
Compliance

The equipment emits Class A, Group 1 disturbances per EN55011, so it is intended for industrial environments.

Restricts use in residential or light-industrial EMC environments.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

The unit has IP20 protection, so it must be installed in a dry, indoor location protected from water and dust ingress.

Determines suitable installation environment and enclosure needs.

Source
“Degree of Protection IP20”
Installation

The pump connection is G1 1/4 male, so mating hoses and fittings must match this thread.

Ensures correct hydraulic connection and avoids adapters.

Source
“Pump connection G1 1/4 male”
Operation

The minimum filling capacity is 18 l and expansion volume is 48 l, so the external loop volume must be considered.

Prevents insufficient fill or overflow in closed external circuits.

Source
“min. filling capacity 18 l”
Selection

The unit is intended for externally closed applications, so open-loop or tank applications are not supported.

Confirms the hydraulic circuit type the chiller is designed for.

Source
“For externally closed applications.”
Maintenance

The refrigerant charge is 1.7 kg with a CO2 equivalent of 2.4 t, which matters for leak checks and F-gas record keeping.

Triggers regulatory leak-check and documentation obligations.

Source
“Refrigerant quantity 1,7 kg”
Installation

The unit weighs 476 kg and measures 938x1288x2003 mm, so floor loading and access routes must be verified.

Ensures the unit can be transported and positioned at the site.

Source
“Overall dimensions WxDxH ** 938x1288x2003 mm”