Introduces the Unichiller 180Tw chiller and its main features
Specpp. 1-2
Performance, temperature, and dimensional data per DIN 12876
p. 2table, 13 rows
p. 1table, 34 rows
Technical data according to DIN 12876
Parameter
Value
min. filling capacity
15 l
Volume of expansion
22 l
Overall dimensions WxDxH **
760x800x1615 mm
Net weight
368 kg
sound pressure level +/- 4 dB(A)
59 dB(A)
Power supply (3 Phase)
460V 3~ 60Hz
max. current (3 Phase)
19,5 A
Fuse (3 phase)
3x20A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S607017
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876 — Unichiller 180Tw (Order-No.: 3019.0045.01)
Parameter
Value
Operating temperature range
-20...40 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,5 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
I / NFL
Cooling power at 15°C
18 kW
Cooling power at 0°C
18 kW
Cooling power at -10°C
13 kW
Cooling power at -20°C
6 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)
Global Warming Potential (GWP)
1397
Refrigerant quantity
2,6 kg
CO2 equivalent
3,6 t
Circulation pump
D3
max. delivery
210 l/min
max. delivery pressure
4,7 bar
Delivery at 1,1 bar
202 l/min
Delivery at 1,5 bar
193 l/min
Delivery at 2,0 bar
179 l/min
Delivery at 2,5 bar
159 l/min
Delivery at 3,0 bar
140 l/min
Delivery at 3,5 bar
115 l/min
Delivery at 4,0 bar
77 l/min
Delivery at 4,5 bar
31 l/min
Pump connection
G1 1/4 male
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
666 l/h
Consumption at water 15°C, flow -10°C
553 l/h
Consumption at water 15°C, flow -20°C
427 l/h
min. cooling water differential pressure
1 bar
max. cooling water pressure
6 bar
Engineering Facts
12 facts · every claim linked to a page
Installation
The chiller is water-cooled and requires a cooling water supply with a minimum differential pressure of 1 bar and a maximum pressure of 6 bar.
Ensures the site cooling water system can provide adequate flow and pressure without overpressurizing the unit.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit is designed for cooling water intake between 5°C and 20°C, and pipes must be insulated if water temperature can fall below the condensation point.
Prevents condensation, corrosion, and performance loss; confirms site cooling water temperature compatibility.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling power drops as cooling water temperature rises, and the required cooling water flow rate may increase.
Affects sizing of the cooling water supply and expected process cooling capacity at site conditions.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only compatible cooling water may be used.
Guides water quality and material compatibility to avoid corrosion or fouling of the cooling circuit.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Compliance
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.
Defines acceptable site power quality and prevents invalid supply combinations that could damage the unit.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
External branch circuit protection according to UL 489 is required.
Mandates additional upstream protection hardware for compliant and safe electrical installation.
Source
“External branch circuit protection according to UL 489 required.”
Installation
Three-phase devices with current consumption less than 63 A are supplied with cable but without a plug.
Requires the installer to provide a suitable plug or hardwired connection for this 19.5 A three-phase unit.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
The refrigerant R-449A is classified A1 with GHS hazard H280, and the unit contains 2.6 kg with a CO2 equivalent of 3.6 t.
Informs refrigerant handling, leak detection, and environmental reporting obligations.
Source
“R-449A (A1, H280)”
Operation
The unit must be operated within an ambient temperature range of 5°C to 40°C.
Ensures the installation location maintains suitable ambient conditions for reliable operation.
Source
“min. ambient temperature 5 °C”
Installation
The unit has IP20 degree of protection, so it must be installed in a dry indoor environment protected from water ingress.
Restricts installation locations and requires additional enclosure protection if exposed to moisture or dust.
Source
“Degree of Protection IP20”
Selection
The chiller provides 18 kW cooling at 15°C and 0°C, 13 kW at -10°C, and 6 kW at -20°C.
Allows the engineer to verify process heat load versus available cooling capacity at the required temperature.
Source
“at -20°C 6 kW”
Installation
The pump connection is G1 1/4 male and the cooling water connection is G3/4 male.
Determines the hose couplings and adapters needed for process and cooling water piping.