Unichiller GL 1650w Datasheet

Contents

  1. Overview p. 1
    Introduces the Unichiller GL 1650w chiller unit
  2. Spec pp. 1-2
    Performance, temperature, and technical data per DIN 12876
  3. p. 2 table, 3 rows
  4. p. 1 table, 34 rows

Technical data according to DIN 12876

ParameterValue
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/26

Unichiller GL 1650w — Technical data according to DIN 12876

ParameterValue
Order-No.5515.0001.01
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at 20°C165 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
UN-numberUN 2857
max. delivery320 l/min
max. delivery pressure4 bar
Delivery at 0,5 bar305 l/min
Delivery at 1,0 bar285 l/min
Delivery at 1,5 bar260 l/min
Delivery at 2,0 bar240 l/min
Delivery at 2,5 bar215 l/min
Delivery at 3,0 bar185 l/min
Delivery at 3,5 bar150 l/min
Delivery at 4,0 bar110 l/min
Delivery at 4,5 bar50 l/min
Pump connectionG1 1/4 male
Cooling water connectionG1 1/4 male
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity17,5 l
Volume of expansion50 l
Overall dimensions WxDxH **918x963x1771 mm
Power supply (3 Phase)400V 3~ 50Hz
Pressure equipment categoryII
Degree of ProtectionIP20

** Overall dimensions WxDxH

Engineering Facts

13 facts · every claim linked to a page
Installation

The chiller requires cooling water with a differential pressure of at least 1 bar and a maximum pressure of 6 bar, so the site water supply must be verified before installation.

Insufficient differential pressure will prevent proper cooling and may cause the unit to trip on high temperature.

Source
“min. cooling water differential pressure 1 bar”
Installation

The unit is water-cooled and must be connected to a cooling water circuit with G1 1/4 male connections, so piping adapters must be planned.

Ensures correct fittings are available and avoids delays during commissioning.

Source
“Cooling water connection G1 1/4 male”
Operation

The cooling water inlet temperature must be between 5°C and 20°C; if it falls below the condensation point, the cooling water pipes inside the unit must be insulated.

Operating outside this range risks condensation, corrosion, or reduced cooling performance.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power drops as cooling water temperature rises, and the required cooling water flow rate may increase, so the water supply must be sized for worst-case conditions.

Prevents undersizing the cooling water supply and ensures stable process temperature control.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water (e.g., low chloride, non-corrosive) should be used.

Incompatible water chemistry can cause corrosion, fouling, or leaks in the cooling circuit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Compliance

The unit is classified as Class A, Group 1 for electromagnetic disturbance to EN55011, which may require additional filtering or separation from sensitive equipment.

Class A equipment is not intended for residential environments and may cause interference; plan EMC measures accordingly.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Safety

Leakage current exceeds 3.5 mA, so a reliable protective earth connection is mandatory and RCD selection must account for this.

Ensures electrical safety and correct earth leakage protection design.

Source
“Attention: leakage current > 3,5mA”
Installation

Three-phase devices with current consumption less than 63 A are supplied with cable but without a plug, so a suitable plug and connection must be provided on site.

Avoids delays and ensures the electrical installation is completed correctly.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Voltage tolerance is ±5% with a simultaneous frequency tolerance of ±2%, but combinations such as -5% voltage and +2% frequency are not allowed.

Prevents operation outside safe limits that could damage the compressor or electronics.

Source
“-5% voltage and +2% frequency -> not allowed!”
Operation

The unit has an IP20 degree of protection, so it must be installed indoors and protected from water ingress and dust.

IP20 is not suitable for wet or dusty environments; installation location must be chosen accordingly.

Source
“Degree of Protection IP20”
Selection

The chiller uses R-744 (CO2) refrigerant with GWP 1 and is classified A1, H280, which affects refrigerant handling and safety requirements.

CO2 refrigerant operates at high pressure and requires specific safety measures and trained personnel.

Source
“R-744 (A1, H280)”
Installation

The overall dimensions are 918x963x1771 mm, and space requirements must be respected, so the installation site must accommodate this footprint and clearance.

Ensures the unit fits in the available space and allows for maintenance access.

Source
“Overall dimensions WxDxH ** 918x963x1771 mm”
Operation

The minimum filling capacity is 17.5 l and the expansion volume is 50 l, so the external circuit volume must be considered when selecting heat transfer fluid quantity.

Prevents underfilling or overfilling the system, which can affect temperature stability and pump performance.

Source
“min. filling capacity 17,5 l”