Aufrechterhaltung der Integrität von Stromnetzen: Agilent Transformatorenöl-Gas-Analyzer
Technical Reference Summary
Covered Models & Document Scope
Agilent Transformatoröl-Gas-Analyzer (TOGA) systems based on the Agilent 8890 GC and 8697 Headspace sampler; three standard TOGA configurations: FID/TCD with packed columns per ASTM D3612 Method A (vacuum extraction); FID/TCD per ASTM D3612 Method C (headspace injection) with methanizer and PLOT columns; FID/TCD per ASTM D3612 Method C (headspace injection) with pre-column backflush, PLOT columns and methanizer bypass, optimized for trace olefins.
Technical Data
| Parameter | Value | Condition |
|---|---|---|
| GC platform | 8890 p.2 ↗ | all TOGA configurations |
| Headspace sampler | 8697 p.2 ↗ | all TOGA configurations |
| Detectors | FID/TCD p.5 ↗ | all three standard configurations |
| Standard configuration 1 | FID/TCD with packed columns per ASTM D3612 Method A (vacuum extraction) p.5 ↗ | TOGA configuration 1 |
| Standard configuration 2 | FID/TCD per ASTM D3612 Method C (headspace injection) with methanizer and PLOT columns p.5 ↗ | TOGA configuration 2 |
| Standard configuration 3 | FID/TCD per ASTM D3612 Method C (headspace injection) with pre-column backflush, PLOT columns and methanizer bypass, opt p.5 ↗ | TOGA configuration 3 |
| Analyzed compounds | H2, O2, N2, CH4, CO and CO2 p.3 ↗ | ASTM D3612-A configuration |
| Valve/column configuration | 2 valves/2 columns/TCD/FID p.3 ↗ | ASTM D3612-A configuration |
| Analysis time | 22.5 min p.3 ↗ | Agilent 8890 GC per ASTM D3612-A |