I832
Technical Reference Summary
Covered Models & Document Scope
Document I 832-EN (1.9.2011) covers recommended cooling water quality and coolant composition for Gardner Denver / Elmo Rietschle pumps; no pump models, sizes or ordering codes are specified.
Technical Data
| Parameter | Value | Condition |
|---|---|---|
| Solid matter | not allowed p.2 ↗ | cooling water |
| pH value | 7 - 8,5 p.2 ↗ | cooling water |
| Carbon hardness | 3 - 8 ° dH p.2 ↗ | cooling water |
| Free carbonic acid | 8 - 15 mg / dm3 p.2 ↗ | cooling water |
| Associated carbonic acid | 8 - 15 mg / dm3 p.2 ↗ | cooling water |
| Aggressive carbonic acid | 0 mg / dm3 p.2 ↗ | cooling water |
| Oxygen | < 10 mg / dm3 p.2 ↗ | cooling water |
| Chloride ions | < 50 mg / dm3 p.2 ↗ | cooling water |
| Sulphate ions | < 250 mg / dm3 p.2 ↗ | cooling water |
| Nitrates and nitrites | < 10 mg / dm3 p.2 ↗ | cooling water |
| CSB (Chemical oxygen requirement) | < 7 mg / dm3 p.2 ↗ | cooling water |
| Ammonia | < 5 mg / dm3 p.2 ↗ | cooling water |
| Iron | < 0,2 mg / dm3 p.2 ↗ | cooling water |
| Manganese | < 0,2 mg / dm3 p.2 ↗ | cooling water |
| Conductivity | < 600 μS / cm p.2 ↗ | cooling water |
| Evaporation residue | < 500 mg / dm3 p.2 ↗ | cooling water |
| Potassium permanganate consumption | < 50 mg / dm3 p.2 ↗ | cooling water |
| Suspended matter | < 3 mg / dm3 p.2 ↗ | cooling water |
| Glycol content in coolant | at least 20 % p.2 ↗ | water and anti-freeze mixture |
Operating Limits
- Minimum glycol content in coolant: 20 % p.2 ↗
- Solid matter in cooling water: not allowed p.2 ↗
- Aggressive carbonic acid in cooling water: 0 mg/dm3 p.2 ↗
- pH value of cooling water: 7 - 8,5 p.2 ↗
- Carbon hardness of cooling water: 3 - 8 °dH p.2 ↗