The chiller uses R-290 (propane, A3 flammable) refrigerant, so the installation location must be assessed for flammable-refrigerant safety and ventilation.
Flammable refrigerant classification affects site safety review, ventilation and local approval before purchase.
Source
“R-290 (A3, H220)”
Selection
Cooling capacity is only 0.3 kW at -20 °C versus 1.5 kW at +15 °C, so the required process load must be checked at the actual working temperature.
Sizing on nominal capacity would undersize the unit at low temperatures.
Source
“at -20°C
0,3 kW”
Installation
The unit requires a 220-240 V single-phase 50 Hz supply with 8 A max current and a 16 A fuse, so the electrical circuit must be sized accordingly.
Determines breaker, cable and socket requirements at the installation site.
Source
“220-240V 1~ 50Hz”
Installation
Voltage and frequency tolerances are ±5 % and ±2 % but must not be combined in opposite directions, so supply quality must be verified.
Prevents installation on a supply that would violate the allowed tolerance envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The chiller is IP20 and must be operated between 5 °C and 40 °C ambient, so it cannot be placed in wet or hot environments.
Defines environmental limits and protection against water/dust ingress at the mounting location.
Source
“Degree of Protection
IP20”
Installation
The unit is air-cooled and cooling capacity drops as ambient temperature rises, so sufficient air flow and cool ambient air are needed.
Poor ventilation will reduce available cooling and may cause overtemperature trips.
Source
“If the ambient temperature rises, the cooling capacity may drop.”
Installation
Space requirements must be respected around the unit, so clearance for air intake/exhaust must be planned.
Insufficient clearance degrades air-cooled condenser performance and service access.
Source
“Please respect space requirements.”
Operation
The plastic pump is not resistant to acetone or polyglycols, so these media must not be used without a more resistant pump option.
Prevents chemical attack and pump failure when selecting heat transfer fluid.
Source
“The plastic pump is not resistant against acetone and polyglycols”
Operation
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than used pure.
Avoids freezing and damage in the cooling circuit at sub-zero set points.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Operation
Minimum filling capacity is 3.8 l and expansion volume is 1.7 l, so the external loop volume must be considered when charging fluid.
Ensures enough heat transfer fluid and expansion space for safe operation.
Source
“min. filling capacity
3,8 l”
Performance
The immersion pump delivers max 29 l/min at 1 bar and 21 l/min at 0.5 bar, so external circuit pressure drop must be checked against this curve.
Determines whether the pump can overcome the pressure drop of the customer loop.
Source
“Delivery at 0,5 bar
21 l/min”
Compliance
The equipment is EMC Class A Group 1, so it is intended for industrial environments and may cause interference in residential areas.
Affects EMC planning and suitability for non-industrial locations.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Compliance
The US-SNAP end-use for this equipment is industrial process refrigeration, so it is not approved for other US end-uses.
Confirms regulatory suitability for the intended US application.
Source
“The US-SNAP end-use for this equipment is the industrial process
refrigeration.”
Maintenance
The refrigerant charge is only 0.16 kg with GWP 0.02, so refrigerant handling and leak-check obligations are minimal but still apply.
Informs service planning and refrigerant record-keeping requirements.