The chiller is water-cooled and requires a cooling water supply with a minimum differential pressure of 1 bar and a maximum pressure of 6 bar.
To ensure the cooling water circuit can provide adequate flow and pressure without exceeding component limits.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit is designed for cooling water intake temperatures between 5°C and 20°C, and if the cooling water temperature falls below the condensation point, the cooling water pipes inside the unit must be insulated.
To avoid condensation and ensure proper operation; insulation may be required depending on site conditions.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling power drops as cooling water temperature increases, and the required cooling water flow rate may increase.
To properly size the cooling water supply and predict performance under actual site conditions.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Safety
The refrigerant is R-290 (propane), classified as A3 and H220 (flammable), with a charge of 0.16 kg.
To assess flammability risks and ensure appropriate ventilation and safety measures during installation and operation.
Source
“R-290 (A3, H220)”
Operation
The plastic pump is not resistant to acetone and polyglycols, so these fluids must be avoided or a more resistant plastic pump must be specified.
To prevent pump damage and ensure compatibility with the heat transfer fluid.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection, it is recommended to mix water with either glysantine or ethylene glycol.
To avoid freezing of the heat transfer fluid at low temperatures and maintain safe operation.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation
The power supply must be 220-240V 1~ 50Hz with a maximum current of 6 A, and the fuse rating is 16 A.
To ensure the electrical supply and protection devices match the unit's requirements.
Source
“Power supply requirement 220-240V 1~ 50Hz”
Compliance
Voltage tolerance is ±5% with a simultaneous frequency tolerance of ±2%, but combinations such as -5% voltage and +2% frequency are not allowed.
To verify that the site power quality is within acceptable limits and avoid invalid combinations that could damage the unit.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
The unit has a degree of protection IP20 and must be operated in ambient temperatures between 5°C and 40°C.
To ensure the installation location meets environmental and electrical safety requirements.
Source
“Degree of Protection IP20”
Installation
The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so suitable cooling water must be used to avoid corrosion.
To select appropriate cooling water quality and prevent corrosion or fouling of the cooling circuit.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Selection
The optional Pt100 sensor connection is only available factory fitted and is for display (not control) of process temperature.
To decide at the time of order whether external temperature monitoring is needed, since it cannot be added later in the field.
Source
“Option: Pt100 sensor connection #10519 to display (not control) e.g. of the process temperature (only available factory fitted, additional charge)”
Installation
The pump connection is G3/4 male and the cooling water connection is G1/2 male, so matching hose couplings are required.
To prepare correct fittings and hoses for installation.