Unichiller 050-H Datasheet

Contents

  1. Overview p. 1
    Introduces the Unichiller 050-H chiller and its main features
  2. Spec pp. 1-2
    Lists performance, temperature, and physical specifications per DIN 12876
  3. p. 2 table, 9 rows
  4. p. 1 table, 34 rows

Technical data according to DIN 12876

ParameterValue
sound pressure level +/- 4 dB(A)62 dB(A)
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)10,5 A
Fuse (3 phase)3x16A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S311391

Technical data according to DIN 12876 — Unichiller 050-H (Order-No.: 3038.0003.01)

CharacteristicValue
Operating temperature range-20...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power2 kW
Cooling power at ambient temperature +20°C
at 100°C5 kW
at 20°C5 kW
at 0°C4,2 kW
at -10°C3 kW
at -20°C1,8 kW
Refrigeration machineair-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity1,03 kg
CO2 equivalent1,4 t
Circulation pump:E1
max. delivery48 l/min
max. delivery pressure3,4 bar
Delivery at 0,3 bar46 l/min
Delivery at 0,5 bar44 l/min
Delivery at 1,0 bar40 l/min
Delivery at 1,5 bar33 l/min
Delivery at 2,0 bar27 l/min
Delivery at 2,5 bar20 l/min
Delivery at 3,0 bar11 l/min
Pump connectionG1 1/4 male
min. filling capacity18 l
Volume of expansion48 l
Overall dimensions WxDxH **740x1160x1165 mm
Net weight268 kg

** см. сноску в оригинале (в тексте страницы пояснение к ** отсутствует).

Engineering Facts

14 facts · every claim linked to a page
Selection

The chiller is rated for an operating temperature range of -20 to 100 °C, so it can serve both sub-ambient and hot-process loops within that window.

Defines whether the unit can cover the required process temperatures before any other sizing is done.

Source
“Operating temperature range -20...100 °C”
Performance

Cooling capacity falls from 5 kW at 20 °C to 1.8 kW at -20 °C, so low-temperature duty needs a much larger unit or a different selection point.

Prevents oversizing assumptions based on nominal capacity when the real operating point is cold.

Source
“at -20°C 1,8 kW”
Installation

The unit requires a 400 V three-phase supply with a 3x16 A fuse, so the electrical infrastructure must be planned accordingly.

Determines the site power feed, breaker/fuse rating and whether a three-phase connection is available.

Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation

Three-phase devices below 63 A are delivered with cable but without a plug, so the customer must provide and fit the site plug.

Affects installation scope and the bill of materials for the electrical hook-up.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

The unit is IP20 and must be installed where ambient temperature stays between 5 and 40 °C, so it is not suitable for wet or hot plant rooms.

Rules out washdown areas and constrains room ventilation and placement.

Source
“Degree of Protection IP20”
Performance

Cooling capacity is quoted at 20 °C room temperature and drops as ambient rises, so the plant room must be kept cool to hold the rating.

Prevents under-sizing when the chiller is installed in a warm or poorly ventilated room.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Safety

The refrigerant is R-449A with GWP 1397 and a 1.4 t CO2 equivalent charge, so refrigerant leak reporting and handling obligations apply.

Triggers F-gas/CO2-equivalent record-keeping and leak-check requirements at the installation site.

Source
“CO2 equivalent 1,4 t”
Safety

The refrigerant is classified A1 with H280, so it is non-flammable but stored under pressure and must be handled as a pressurized gas hazard.

Informs risk assessment, ventilation and service procedures for the refrigeration circuit.

Source
“R-449A (A1, H280)”
Installation

The pump connection is G1 1/4 male, so hoses and fittings must match that thread size.

Determines the hydraulic interface and the adapters needed for the external loop.

Source
“Pump connection G1 1/4 male”
Operation

The pump delivers 48 l/min at zero head but only 11 l/min at 3.0 bar, so system pressure drop must be checked against the pump curve.

Avoids selecting a unit whose pump cannot push the required flow through a high-resistance loop.

Source
“Delivery at 3,0 bar 11 l/min”
Installation

The unit needs a minimum filling capacity of 18 l and has a 48 l expansion volume, so the external loop volume must be sized within these limits.

Sets the minimum heat-transfer-fluid charge and the expansion tank capacity for the installation.

Source
“min. filling capacity 18 l”
Installation

The unit weighs 268 kg and measures 740x1160x1165 mm, so floor loading and access routes must be verified before delivery.

Affects rigging, doorway clearance and floor load capacity at the installation point.

Source
“Net weight 268 kg”
Compliance

The unit is EMC Class A Group 1, so it is intended for industrial environments and may cause interference in residential areas.

Determines whether the installation location is appropriate and whether EMC mitigation is needed.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Operation

The sound pressure level is 62 dB(A), so noise-sensitive areas may need acoustic treatment or separation.

Relevant when the chiller is placed near occupied workspaces.

Source
“sound pressure level +/- 4 dB(A) 62 dB(A)”