Contents

  1. Overview p. 1
    Introduces the Unichiller 100w chiller unit and its main features
  2. Spec pp. 1-2
    Lists performance, temperature, and dimensional data per DIN 12876
  3. p. 2 table, 13 rows
  4. p. 1 table, 35 rows

Technical data according to DIN 12876

ParameterValue
min. filling capacity18 l
Volume of expansion48 l
Overall dimensions WxDxH **740x1160x1050 mm
Net weight274 kg
sound pressure level +/- 4 dB(A)58 dB(A)
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)8,5 A
Fuse (3 phase)3x10A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S528930

** Please respect space requirements. See operating conditions at www.huber-online.com

Unichiller 100w — Technical data according to DIN 12876

ParameterValue
Order-No.3059.0009.01
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at ambient temperature +20°C at 20°C10 kW
Cooling power at ambient temperature +20°C at 0°C8,6 kW
Cooling power at ambient temperature +20°C at -10°C6 kW
Cooling power at ambient temperature +20°C at -20°C3,9 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity1,03 kg
CO2 equivalent1,4 t
Circulation pumpE1
max. delivery48 l/min
max. delivery pressure3,4 bar
Delivery at 0,3 bar46 l/min
Delivery at 0,5 bar44 l/min
Delivery at 1,0 bar40 l/min
Delivery at 1,5 bar33 l/min
Delivery at 2,0 bar27 l/min
Delivery at 2,5 bar20 l/min
Delivery at 3,0 bar11 l/min
Pump connectionG1 1/4 male
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 20°C348 l/h
Consumption at water 15°C, flow 0°C330 l/h
Consumption at water 15°C, flow -10°C270 l/h
Consumption at water 15°C, flow -20°C240 l/h
min. cooling water differential pressure0,5 bar
max. cooling water pressure6 bar

Engineering Facts

13 facts · every claim linked to a page
Installation

The chiller requires a three-phase 400 V supply with a 3x10 A fuse, so the electrical installation must be sized accordingly.

Determines the site power supply, cable and protection device required before installation.

Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation

The unit is water-cooled and needs a cooling water supply with at least 0.5 bar differential pressure and no more than 6 bar.

Cooling water pressure must be verified on site to ensure sufficient flow and avoid overpressure damage.

Source
“min. cooling water differential pressure 0,5 bar”
Installation

Cooling water inlet temperature must be kept between 5 °C and 20 °C, and pipes must be insulated if condensation can occur.

Out-of-range cooling water temperature reduces cooling capacity and can cause condensation and corrosion.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling capacity drops significantly as the required process temperature decreases, from 10 kW at +20 °C to 3.9 kW at -20 °C.

The chiller must be selected against the actual cooling load at the lowest required process temperature.

Source
“Cooling power at ambient temperature +20°C”
Performance

The circulation pump delivers 48 l/min maximum and its flow falls as pressure rises, reaching only 11 l/min at 3.0 bar.

External circuit pressure drop must be checked to confirm the pump can provide the required flow.

Source
“max. delivery 48 l/min”
Installation

The pump connection is G1 1/4 male and the cooling water connection is G1/2 male, so matching hoses and couplings are needed.

Ensures correct fittings and hoses are ordered and available for mechanical installation.

Source
“Pump connection G1 1/4 male”
Operation

The unit is rated IP20 and must be operated in ambient temperatures between 5 °C and 40 °C.

Installation location must provide adequate ventilation and avoid high ambient temperatures that reduce performance.

Source
“max. ambient temperature 40 °C”
Safety

The refrigerant R-449A is classified A1 with GHS hazard H280, so refrigerant handling and leak procedures must account for a pressurized gas hazard.

Affects site safety documentation, leak detection and service procedures for the refrigeration circuit.

Source
“R-449A (A1, H280)”
Compliance

The unit is classified as pressure equipment under Article 4.3 PED, which affects documentation and conformity requirements.

Needed for regulatory compliance and acceptance of the equipment on site.

Source
“Pressure equipment category Art. 4.3 PED”
Installation

Three-phase devices below 63 A are supplied with a cable but without a plug, so a suitable plug must be provided on site.

Prevents delays at commissioning because the electrical contractor must supply and fit the plug.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation

Voltage and frequency tolerances are ±5 % and ±2 % respectively, but not all combinations are allowed.

Site power quality must be checked to avoid invalid supply combinations and equipment malfunction.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Maintenance

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Water quality and treatment must be selected to prevent corrosion and fouling of these materials.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation

The unit weighs 274 kg and measures 740x1160x1050 mm, so floor loading and access routes must be planned.

Needed for rigging, transport route and installation space planning.

Source
“Overall dimensions WxDxH ** 740x1160x1050 mm”