The chiller is rated for an operating temperature range of -20 to 40 °C, so the process must stay within these limits.
Defines whether the unit can cover the required process temperatures.
Source
“Operating temperature range -20...40 °C”
| Parameter | Value |
|---|---|
| Operating temperature range | -20...40 °C |
| temperature set point / display | 5,7" colour Touchscreen |
| Internal temperature sensor | Pt100 |
| Sensor external connection | Pt100 |
| Interface digital | Ethernet, USB (Host u. Device), RS232 |
| Temperature stability at -10°C | 0,5 K |
| Safety classification | I / NFL |
| Cooling power at 15°C | 21 kW |
| Cooling power at 0°C | 21 kW |
| Cooling power at -10°C | 13,5 kW |
| Cooling power at -20°C | 7,5 kW |
| Refrigeration machine | air-cooled, CFC- and HCFC-free |
| Refrigerant (ASHRAE, GHS) | R-449A (A1, H280) |
| Global Warming Potential (GWP) | 1397 |
| Circulation pump: | D3 |
| max. delivery | 210 l/min |
| max. delivery pressure | 4,7 bar |
| Delivery at 1,1 bar | 202 l/min |
| Delivery at 1,5 bar | 193 l/min |
| Delivery at 2,0 bar | 179 l/min |
| Delivery at 2,5 bar | 159 l/min |
| Delivery at 3,0 bar | 140 l/min |
| Delivery at 3,5 bar | 115 l/min |
| Delivery at 4,0 bar | 77 l/min |
| Delivery at 4,5 bar | 31 l/min |
| Pump connection | G1 1/4 male |
| min. filling capacity | 14 l |
| Volume of expansion | 39 l |
| Overall dimensions WxDxH ** | 905x2172x1900 mm |
| Power supply (3 Phase) | 400V 3~ 50Hz |
| Pressure equipment category | I |
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
| max. ambient temperature | 40 °C |
** см. сноску в оригинале (в тексте страницы пояснение к ** отсутствует)
The chiller is rated for an operating temperature range of -20 to 40 °C, so the process must stay within these limits.
Defines whether the unit can cover the required process temperatures.
“Operating temperature range -20...40 °C”
Cooling capacity drops from 21 kW at 0 °C to 7.5 kW at -20 °C, so low-temperature duty needs a larger unit or lower load.
Cooling capacity at the actual operating temperature determines feasibility and sizing.
“at -20°C 7,5 kW”
The unit requires a 400 V three-phase 50 Hz supply, so site power must be three-phase.
Electrical supply compatibility must be confirmed before ordering and installation.
“Power supply (3 Phase) 400V 3~ 50Hz”
Three-phase devices below 63 A are delivered with cable but without a plug, so the customer must provide the site plug.
Affects electrical installation scope and what must be procured on site.
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
The unit is IP20, so it must be installed in a dry indoor location protected from water and dust ingress.
Environmental protection class limits where the chiller can be installed.
“Degree of Protection IP20”
Ambient temperature must stay between 5 and 40 °C, and cooling capacity may fall if ambient rises.
Site ambient conditions directly affect available cooling performance.
“If the ambient temperature rises, the cooling capacity may drop.”
The unit is air-cooled and uses R-449A refrigerant with GWP 1397, so ventilation and refrigerant reporting may be required.
Refrigerant type and GWP affect room ventilation, safety and environmental compliance.
“Refrigerant (ASHRAE, GHS) R-449A (A1, H280)”
The chiller has overall dimensions 905 x 2172 x 1900 mm, so access routes and floor space must accommodate it.
Physical size determines rigging, doorway clearance and installed footprint.
“Overall dimensions WxDxH ** 905x2172x1900 mm”
Space requirements must be respected, so clearance around the air-cooled unit must be planned.
Air-cooled chillers need adequate clearance for heat rejection and service access.
“** Please respect space requirements. See operating conditions at www.huber-online.com”
The pump connection is G1 1/4 male, so mating hoses and fittings must match this thread.
Ensures correct hydraulic connection hardware is ordered.
“Pump connection G1 1/4 male”
Minimum filling capacity is 14 l and expansion volume is 39 l, so the external loop volume must be considered.
Loop volume affects fill quantity, expansion behaviour and heat transfer fluid selection.
“min. filling capacity 14 l”
Pump delivery falls from 210 l/min at zero head to 31 l/min at 4.5 bar, so system pressure drop must be checked against the pump curve.
Available flow at the actual system pressure drop determines whether the process loop can be supplied.
“max. delivery 210 l/min”
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and some combinations are not allowed.
Site power quality must be verified to avoid invalid supply combinations and equipment stress.
“-5% voltage and +2% frequency -> not allowed!”
The equipment is EMC Class A Group 1, so it may cause radio interference in residential areas.
EMC class affects installation location and potential interference with sensitive equipment.
“Classification (disturbance) to EN55011: Class A, Group 1”