Selection
The unit is rated for an operating temperature range of -20 to 100 °C, so it must be matched to the process temperature window.
Defines whether the chiller can cover the required process temperatures at all.
Source
“Operating temperature range
-20...100 °C”
Performance
Cooling capacity falls from 1.2 kW at 15 °C to 0.25 kW at -20 °C, so low-temperature duty needs a larger unit or lower heat load.
Cooling capacity must be checked at the actual operating temperature, not only at nominal conditions.
Source
“at 15°C
1,2 kW
at 0°C
1 kW
at -10°C
0,7 kW
at -20°C
0,25 kW”
Installation
The refrigeration machine is air-cooled, so sufficient air flow and ambient temperature limits must be respected at the installation site.
Air-cooled units reject heat to the room and require adequate ventilation and clearance.
Source
“Refrigeration machine
air-cooled, CFC- and
HCFC-free”
Installation
The permissible ambient temperature is 5 to 40 °C, so the room must stay within this range for reliable operation.
Ambient temperature outside this range can reduce cooling capacity or trip the unit.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Performance
Cooling capacity data are valid at 20 °C room temperature and may drop if ambient temperature rises.
Selection calculations must account for actual room temperature, not just the datasheet values.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
The pump connection is G3/4 male, so hoses and adapters must match this thread.
Ensures correct fitting of hoses and avoids leaks or adapters at commissioning.
Source
“Pump connection
G3/4 male”
Installation
The minimum filling capacity is 3.8 l and the expansion tank is 1.7 l, so the external loop volume and fluid expansion must be considered.
Prevents underfilling and overflow or pressure issues in closed loops.
Source
“min. filling capacity
3,8 l
expansion tank
1,7 l”
Operation
The pump delivers 21 l/min at 0.5 bar but only 6 l/min at 2.0 bar, so system pressure drop directly limits available flow.
Flow must be checked against the actual pressure drop of the external circuit.
Source
“at 0,5 bar
21 l/min
at 1,0 bar
17 l/min
at 1,5 bar
11 l/min
at 2,0 bar
6 l/min”
Safety
The unit has adjustable overtemperature protection according to DIN 12876, which must be set for the application.
Overtemperature protection is a key safety function and must be configured during commissioning.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Safety
The refrigerant is R-449A with GHS classification H280, so refrigerant handling and leak response must follow safety rules.
Affects safety procedures, ventilation and service access for refrigerant work.
Source
“R-449A (A1, H280)”
Compliance
The refrigerant has a GWP of 1397 and a charge of 0.38 kg, giving 0.5 t CO2 equivalent, which matters for F-gas reporting.
Determines leak-check and documentation obligations under refrigerant regulations.
Source
“Global Warming Potential (GWP)
1397
Refrigerant quantity
0,38 kg
CO2 equivalent
0,5 t”
Installation
The power supply requirement is 220-240 V single/two-phase 50/60 Hz with a maximum current of 14.5 A and a 16 A fuse.
Electrical supply, cable and protection must be sized for this current and fuse rating.
Source
“Power supply requirement
220-240V 1~/2~ 50/60Hz
max. current
14,5 A
Fuse
16 A”
Installation
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and some combinations are not allowed.
Poor site power quality can invalidate warranty or cause unreliable operation.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Operation
The plastic pump is not resistant to acetone and polyglycols, so these fluids must be avoided or a more resistant pump specified.
Prevents chemical attack and premature pump failure in fluid selection.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”