Selection
The chiller is rated for an operating temperature range of -10 to 100 °C, so the process must stay within these limits.
Defines the application window and excludes processes requiring lower or higher temperatures.
Source
“Operating temperature range
-10...100 °C”
Selection
Cooling capacity drops with lower evaporating temperature, from 2.2 kW at 15 °C to 1 kW at -10 °C, so size the unit for the coldest duty point.
Prevents undersizing when the process requires low-temperature cooling.
Source
“at 15°C
2,2 kW
at 0°C
1,6 kW
at -10°C
1 kW”
Installation
The unit requires a 220-240 V single-phase 50 Hz supply with up to 15 A current and a 16 A fuse.
Determines electrical supply, breaker rating and cabling for the installation.
Source
“Power supply requirement
220-240V 1~ 50Hz
max. current
15 A
Fuse
16 A”
Installation
The chiller is air-cooled and must be installed where ambient temperature stays between 5 °C and 40 °C.
Ambient conditions affect cooling performance and reliable operation of the air-cooled refrigeration machine.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Performance
Cooling capacity is declared at 20 °C room temperature and may fall if ambient temperature rises.
Installation in a hot room can reduce available cooling capacity below the datasheet values.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
The pump connection is G3/4 male, so hoses and fittings must match this thread.
Ensures correct plumbing connection and avoids adapters or leaks.
Source
“Pump connection
G3/4 male”
Operation
The pump delivers 25 l/min maximum and 2.5 bar maximum pressure, with flow falling as pressure rises.
Needed to check whether the pump can overcome the pressure drop of the external circuit.
Source
“max. delivery
25 l/min
max. delivery pressure
2,5 bar”
Operation
The minimum filling capacity is 3.8 l and expansion volume is 1.7 l, so the loop must be filled and expansion accommodated accordingly.
Prevents insufficient filling and overpressure from thermal expansion.
Source
“min. filling capacity
3,8 l
Volume of expansion
1,7 l”
Safety
The refrigerant is R-449A with GHS hazard H280, UN 2857, and GWP 1397, so refrigerant handling and leak response must follow safety rules.
Affects safety classification, ventilation requirements and environmental reporting.
Source
“Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)”
Safety
The plastic pump is not resistant to acetone and polyglycols, so these media must not be used without a more resistant pump.
Prevents chemical attack and pump failure when selecting heat transfer fluid.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than used alone.
Avoids freezing and damage when operating near or below 0 °C.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Compliance
The unit is classified Class A, Group 1 for electromagnetic disturbance to EN55011, which matters for the electrical environment.
Class A equipment may require EMC precautions in residential or sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation
Voltage and frequency tolerances are ±5% and ±2% respectively, but not all combinations are allowed.
Ensures the supply quality is within the allowed envelope before commissioning.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
The degree of protection is IP20, so the unit must be protected from water and dust ingress.
Restricts installation location to dry, clean indoor areas.
Source
“Degree of Protection
IP20”