Unichiller P022w-H OLÉ Technical Data

Contents

  1. Overview p. 1
    Product name and cover page for the chiller
  2. Spec p. 2
    Technical data according to DIN 12876 in a table
  3. p. 2 table, 4 rows

Technical data according to DIN 12876

ParameterValue
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.1/24

Engineering Facts

13 facts · every claim linked to a page
Installation

The chiller requires cooling water with a minimum differential pressure of 1 bar and a maximum pressure of 6 bar, so the site water supply must be checked before installation.

Insufficient differential pressure will prevent proper cooling; excessive pressure may damage the water circuit.

Source
“min. cooling water differential pressure 1 bar”
Installation

The unit is water-cooled and must be connected to a cooling water supply with G1/2 male connections, so piping adapters and a drain valve should be planned.

Ensures correct mechanical connection and avoids delays during commissioning.

Source
“Cooling water connection G1/2 male”
Operation

The cooling water inlet temperature must be between 5°C and 20°C; below the condensation point the cooling water pipes inside the unit must be insulated.

Operating outside this range risks condensation, corrosion, or reduced cooling performance.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power drops as cooling water temperature rises, and the required cooling water flow rate may increase, so the water supply must be sized with margin.

Prevents undersizing the cooling water circuit and ensures the chiller meets process load.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Safety

The plastic pump is not resistant to acetone or polyglycols, so these fluids must be avoided or a more resistant pump option ordered.

Using incompatible fluids can cause pump failure and leaks.

Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation

For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water below 0°C.

Prevents freezing and damage to the evaporator or pump when operating near or below 0°C.

Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Compliance

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and combinations such as -5% voltage with +2% frequency are not allowed.

Ensures the electrical supply stays within safe limits and avoids invalid operating conditions.

Source
“-5% voltage and +2% frequency -> not allowed!”
Installation

Single- and two-phase devices are supplied with a power cable and country-specific plug, which must be specified at ordering.

Avoids missing or incorrect plug type and simplifies electrical installation.

Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”
Installation

Three-phase devices below 63A are supplied with cable but without plug, so a suitable plug must be provided on site.

Prevents delays because the plug is not included and must be sourced separately.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation

The unit has an autostart function for power failure, so it will restart automatically after power is restored.

Important for unattended processes and for assessing restart behavior after power loss.

Source
“Autostart function for power failure”
Maintenance

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water should be used to avoid corrosion.

Guides water quality requirements and prevents corrosion or fouling of the cooling circuit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Selection

The chiller uses refrigerant R-449A with GWP 1397, which matters for environmental compliance and refrigerant handling.

Affects environmental permitting, leak detection requirements, and service planning.

Source
“R-449A (A1, H280)”
Installation

The unit has protection degree IP20 and must be installed in an environment between 5°C and 40°C ambient temperature.

Ensures the installation location meets electrical protection and ambient conditions.

Source
“max. ambient temperature 40 °C”