Unichiller P100w Datasheet

Contents

  1. Overview p. 1
    Introduces the Unichiller P100w chiller and its main features
  2. Spec pp. 1-2
    Performance, temperature, and physical specifications per DIN 12876
  3. p. 2 table, 17 rows
  4. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
Consumption at water 15°C, flow -10°C270 l/h
Consumption at water 15°C, flow -20°C240 l/h
min. cooling water differential pressure0,5 bar
max. cooling water pressure6 bar
min. filling capacity18 l
Volume of expansion48 l
Overall dimensions WxDxH **740x1160x1050 mm
Net weight311 kg
sound pressure level +/- 4 dB(A)58 dB(A)
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)13 A
Fuse (3 phase)3x16A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S503730

** Please respect space requirements. See operating conditions at www.huber-online.com

Unichiller P100w — Technical data according to DIN 12876

ParameterValue
Order-No.3059.0011.01
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at ambient temperature +20°C
at 20°C10 kW
at 0°C7,8 kW
at -10°C5,3 kW
at -20°C3,1 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity1,03 kg
CO2 equivalent1,4 t
Circulation pumpE2
max. delivery130 l/min
max. delivery pressure5,7 bar
Delivery at 2,4 bar116 l/min
Delivery at 2,5 bar115 l/min
Delivery at 3,0 bar108 l/min
Delivery at 3,5 bar100 l/min
Delivery at 4,0 bar92 l/min
Delivery at 4,5 bar80 l/min
Delivery at 5,0 bar59 l/min
Delivery at 5,5 bar20 l/min
Pump connectionG1 1/4 male
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 20°C348 l/h
Consumption at water 15°C, flow 0°C330 l/h

Engineering Facts

12 facts · every claim linked to a page
Installation

The chiller is water-cooled and requires a cooling water supply with a differential pressure of at least 0.5 bar and no more than 6 bar.

Ensures the cooling water circuit is sized correctly and protected from overpressure during installation.

Source
“min. cooling water differential pressure 0,5 bar max. cooling water pressure 6 bar”
Installation

The unit must be supplied with 400 V three-phase power and protected by a 3x16 A fuse.

Determines electrical supply, cable sizing and breaker selection for the installation site.

Source
“Power supply (3 Phase) 400V 3~ 50Hz max. current (3 Phase) 13 A Fuse (3 phase) 3x16A”
Installation

Three-phase devices drawing less than 63 A are delivered with a cable but without a plug, so the customer must provide the plug.

Affects electrical installation planning and procurement of the mating plug.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation

The cooling water inlet temperature must be kept between 5 °C and 20 °C, and pipes must be insulated if condensation can occur.

Prevents condensation, corrosion and loss of cooling performance during operation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling capacity is rated at 20 °C room temperature and 15 °C cooling water inlet with 0.5 bar differential pressure, so higher water temperatures reduce capacity.

Allows correct interpretation of the published cooling power figures when selecting the unit.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 0,5 bar differential pressure between cooling water inlet and -outlet.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and material compatibility checks to avoid corrosion and fouling.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Compliance

Voltage and frequency tolerances must be applied together: ±5 % voltage with ±2 % frequency, but not opposite-sign deviations.

Defines acceptable site power quality and prevents invalid supply combinations.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety

The refrigerant R-449A is classified A1 with GHS hazard H280, and the unit contains 1.03 kg corresponding to 1.4 t CO2 equivalent.

Informs refrigerant handling, leak reporting and environmental compliance obligations.

Source
“R-449A (A1, H280)”
Installation

The unit has IP20 protection and must be installed where ambient temperature stays between 5 °C and 40 °C.

Restricts installation location to dry indoor areas with adequate ventilation and climate control.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The unit requires a minimum filling capacity of 18 l and has 48 l expansion volume, and space requirements must be respected.

Ensures the external circuit volume and installation clearances are planned correctly.

Source
“min. filling capacity 18 l Volume of expansion 48 l”
Performance

The circulation pump delivers up to 130 l/min at 5.7 bar, but flow drops sharply at high pressure, e.g. 20 l/min at 5.5 bar.

Allows checking whether the pump can overcome the pressure drop of the external application.

Source
“max. delivery 130 l/min max. delivery pressure 5,7 bar”
Operation

The unit is intended for externally closed applications and has an atmospheric open expansion tank.

Prevents misapplication in open-loop or unpressurised external circuits.

Source
“For externally closed applications.”