The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this power configuration.
Determines electrical infrastructure and whether the unit can be installed at the site.
Source
“Power supply (3 Phase) 460V 3~ 60Hz”
| Parameter | Value |
|---|---|
| min. filling capacity | 18 l |
| Volume of expansion | 48 l |
| Overall dimensions WxDxH ** | 940x1290x1130 mm |
| Power supply (3 Phase) | 460V 3~ 60Hz |
| Pressure equipment category | I |
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
| max. ambient temperature | 40 °C |
| from Serial-No.: | 1.0/21 |
** Please respect space requirements. See operating conditions at www.huber-online.com
| Parameter | Value |
|---|---|
| Order-No. | 3039.0039.01 |
| Operating temperature range | -20...40 °C |
| temperature set point / display | 5,7" colour Touchscreen |
| Internal temperature sensor | Pt100 |
| Sensor external connection | Pt100 |
| Temperature stability at -10°C | 0,5 K |
| Interface digital | Ethernet, USB (Host u. Device), RS232 |
| Safety classification | I / NFL |
| Cooling power at ambient temperature +20°C at 20°C | 23 kW |
| Cooling power at ambient temperature +20°C at 0°C | 13,5 kW |
| Cooling power at ambient temperature +20°C at -10°C | 9 kW |
| Cooling power at ambient temperature +20°C at -20°C | 5,5 kW |
| Refrigeration machine | water-cooled, CFC- and HCFC-free |
| Refrigerant (ASHRAE, GHS) | R-449A (A1, H280) |
| Global Warming Potential (GWP) | 1397 |
| Circulation pump | E2 |
| max. delivery | 140 l/min |
| max. delivery pressure | 5,3 bar |
| Delivery at 2,8 bar | 126 l/min |
| Delivery at 3,0 bar | 124 l/min |
| Delivery at 3,5 bar | 115 l/min |
| Delivery at 4,0 bar | 103 l/min |
| Delivery at 4,5 bar | 83 l/min |
| Delivery at 5,0 bar | 43 l/min |
| Pump connection | G1 1/4 male |
| Cooling water connection | G3/4 male |
| Consumption at water 15°C, flow 20°C | 744 l/h |
| Consumption at water 15°C, flow 0°C | 540 l/h |
| Consumption at water 15°C, flow -10°C | 414 l/h |
| Consumption at water 15°C, flow -20°C | 324 l/h |
| min. cooling water differential pressure | 1 bar |
| max. cooling water pressure | 6 bar |
The chiller requires a three-phase 460 V 60 Hz supply, so the site must provide this power configuration.
Determines electrical infrastructure and whether the unit can be installed at the site.
“Power supply (3 Phase) 460V 3~ 60Hz”
External branch circuit protection per UL 489 must be provided by the installer.
Affects electrical panel design and compliance before commissioning.
“External branch circuit protection according to UL 489 required.”
Three-phase devices drawing less than 63 A are supplied with cable but no plug, so a suitable plug/disconnect must be field-provided.
Impacts electrical connection planning and bill of materials.
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Cooling water inlet must be between 5 °C and 20 °C, and pipes must be insulated if water temperature can fall below the condensation point.
Defines cooling water supply requirements and condensation/insulation measures.
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so water quality must be compatible.
Guides cooling water quality and material compatibility to avoid corrosion or fouling.
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Cooling water pressure must be at least 1 bar differential and no more than 6 bar.
Ensures adequate flow and prevents overpressure damage to the water circuit.
“min. cooling water differential pressure 1 bar”
Cooling capacity drops as cooling water temperature rises, and required cooling water flow may increase.
Affects sizing of the cooling water supply and expected performance at site conditions.
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Voltage and frequency tolerances are ±5% and ±2% respectively, but certain combinations (e.g., -5% voltage with +2% frequency) are not allowed.
Prevents operation outside allowed supply quality and avoids invalid tolerance combinations.
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
The unit is EMC Class A Group 1, which may require additional measures in residential or sensitive environments.
Informs EMC planning and potential restrictions on installation location.
“Classification (disturbance) to EN55011: Class A, Group 1”
The refrigerant is R-449A with GHS classification H280 (pressurized gas), so handling and ventilation precautions apply.
Relevant for safety assessments, refrigerant handling, and leak response planning.
“R-449A (A1, H280)”
The unit is intended for externally closed applications, which constrains the hydraulic circuit design.
Ensures the chiller is applied only in compatible closed-loop external circuits.
“For externally closed applications.”
The pump provides high discharge pressure (max 5.3 bar) for applications with high pressure drops.
Helps match pump capability to external circuit pressure loss.
“Circulating pumps with a high discharge pressure for applications with high pressure drops.”
Ambient temperature must remain between 5 °C and 40 °C for proper operation.
Defines the allowable installation environment and ventilation/cooling needs.
“min. ambient temperature 5 °C”
The expansion tank is atmospheric open and has a digital level indicator, so level monitoring and maintenance access are needed.
Affects routine maintenance and fluid level checks.
“Housing, atmospheric open expansion tank and copper soldered evaporator made of stainless steel. With digital level indicator.”