Unistat GL 535w Temperature Control System Datasheet

Contents

  1. Overview p. 1
    Introduces the Unistat GL 535w unit and its main features
  2. Spec pp. 1-2
    Performance, temperature range, and technical data per DIN 12876
  3. p. 2 table, 17 rows
  4. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
max. permissible kin. viscosity100 mm²/s
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 0°C2100 l/h
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure6 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **730x804x1738 mm
Net weight531 kg
Power supply requirement400V 3~ 50Hz
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.1/24

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterValue
Operating temperature range-50...200 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power12 kW
Cooling power with Thermooil at 200°C23 kW
Cooling power with Thermooil at 100°C23 kW
Cooling power with Thermooil at 20°C23 kW
Cooling power with Ethanol at 0°C20 kW
Cooling power with Ethanol at -20°C12,5 kW
Cooling power with Ethanol at -40°C5,5 kW
Cooling power with Ethanol at -50°C2,2 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
Refrigerant quantity3,5 kg
CO2 equivalent0,0 t
Circulation pump:MK pump
max. delivery196 l/min
max. delivery pressure2,5 bar
Delivery at 0,5 bar175 l/min
Delivery at 1,0 bar152 l/min
Delivery at 1,5 bar123 l/min
Delivery at 2,0 bar86 l/min
Pump connectionM38x1,5 male

Engineering Facts

14 facts · every claim linked to a page
Installation

The unit requires a 400 V three-phase supply, so the electrical installation must be planned for a 3~ 50 Hz feed.

Determines the site power distribution, cable sizing and whether a suitable three-phase connection is available.

Source
“Power supply requirement 400V 3~ 50Hz”
Installation

The cooling water circuit must be supplied at 1–4 bar differential pressure and must not exceed 6 bar, so the building water system needs a pressure regulator or check.

Prevents damage to the water-cooled condenser and ensures the specified cooling capacity is achieved.

Source
“min. cooling water differential pressure 1 bar max. cooling water differential pressure 4 bar max. cooling water pressure 6 bar”
Installation

The unit is designed for cooling water intake between 5 °C and 20 °C, and pipes must be insulated if the water can fall below the dew point.

Cooling water outside this range reduces capacity or causes condensation, so the site water temperature must be checked before selection.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C. When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Cooling capacity is rated at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure, so actual capacity will differ if site conditions deviate.

All published cooling capacities are conditional; the engineer must correct for actual ambient and cooling water conditions.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -outlet.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Incompatible water chemistry can corrode or foul the condenser and reduce cooling performance.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Installation

Voltage and frequency tolerances are ±5 % and ±2 % respectively, but a −5 % voltage combined with +2 % frequency is not allowed.

Defines the acceptable supply quality at the installation point and flags a prohibited combination that could damage the compressor.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2% Example -5% voltage and +2% frequency -> not allowed!”
Installation

Three-phase devices drawing less than 63 A are delivered with a cable but without a plug, so the customer must provide the final connection.

Affects the electrical installation scope and the need for a suitable isolator or plug at site.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety

The unit is classified IP20, so it must be installed in a dry indoor location protected from water ingress.

Prevents specifying the unit for washdown or outdoor areas where moisture could enter the enclosure.

Source
“Degree of Protection IP20”
Installation

Ambient temperature must stay between 5 °C and 40 °C, so the room ventilation and heating must be checked.

Operation outside this range can trip the unit or reduce cooling capacity and reliability.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The unit weighs 531 kg and measures 730×804×1738 mm, so floor loading and access routes must be verified.

Determines transport route, floor strength and required clearances at the installation site.

Source
“Overall dimensions WxDxH ** 730x804x1738 mm Net weight 531 kg”
Operation

The pump connection is M38x1.5 male with a Y-shaped bore per DIN 3863, so mating hoses must use the specified ball socket and sleeve nut.

Ensures correct hose/pipe fittings are ordered and prevents leaks at the circulation connections.

Source
“Pump connection M38x1,5 male”
Operation

The pump delivers 196 l/min at zero head but only 86 l/min at 2.0 bar, so the external circuit pressure drop must be checked against the pump curve.

Prevents selecting the unit for an external loop whose pressure drop would starve the required flow.

Source
“max. delivery 196 l/min max. delivery pressure 2,5 bar Delivery at 2,0 bar 86 l/min”
Selection

The refrigerant is R-744 with GWP 1 and a charge of 3.5 kg, giving a CO2 equivalent of 0.0 t.

Supports environmental compliance and refrigerant reporting; R-744 is a natural refrigerant with negligible GWP.

Source
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280) Global Warming Potential (GWP) 1 Refrigerant quantity 3,5 kg CO2 equivalent 0,0 t”
Safety

The safety classification is III / FL, which defines the over-temperature protection category under DIN 12876.

Confirms the unit's safety category for use with flammable or non-flammable fluids and for risk assessment.

Source
“Safety classification III / FL”