Contents

  1. Overview p. 1
    Product introduction and general description of the Unistat GL P570w unit
  2. Spec pp. 1-2
    Technical data, performance figures and operating parameters per DIN 12876
  3. p. 2 table, 19 rows
  4. p. 1 table, 28 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity100 mm²/s
Cooling water connectionG3/4 male
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure6 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1771 mm
Power supply requirement400V 3~ 50Hz
Pressure equipment categoryII
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/24

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unistat GL P570w (Order-No.: 5041.0002.01)

CharacteristicValue
Operating temperature range-50...200 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power48 kW
Cooling power with Thermooil at 200°C57 kW
Cooling power with Thermooil at 100°C57 kW
Cooling power with Thermooil at 20°C57 kW
Cooling power with Ethanol at 0°C50 kW
Cooling power with Ethanol at -20°C35 kW
Cooling power with Ethanol at -40°C19 kW
Cooling power with Ethanol at -50°C12 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
UN-numberUN 2857
Circulation pump: MK pump max. delivery201 l/min
Circulation pump: MK pump max. delivery pressure5,3 bar
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min

Таблица приведена в исходном виде (характеристика — значение); данные дословно по тексту страницы.

Engineering Facts

14 facts · every claim linked to a page
Installation

The unit requires a 400 V three-phase 50 Hz supply, so the site must provide a suitable three-phase power connection.

Determines electrical infrastructure and whether the installation site can support the unit.

Source
“Power supply requirement 400V 3~ 50Hz”
Installation

The cooling water connection is G3/4 male and requires a differential pressure between 1 and 4 bar, with maximum cooling water pressure 6 bar.

Needed to design the cooling water supply and ensure adequate flow and pressure without overpressurizing the unit.

Source
“Cooling water connection G3/4 male min. cooling water differential pressure 1 bar max. cooling water differential pressure 4 bar max. cooling water pressure 6 bar”
Installation

The unit is water-cooled and must be supplied with cooling water between 5 °C and 20 °C; below the condensation point the cooling water pipes must be insulated.

Cooling water temperature affects cooling capacity and requires insulation to prevent condensation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C. When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Cooling capacity drops as cooling water temperature rises, and the required cooling water flow rate may increase.

The published cooling capacities are valid only at 15 °C cooling water inlet and 1 bar differential pressure, so system design must account for actual site conditions.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The pump connection is M38x1,5 male and pipework or flexible hoses must use ball socket according to DIN 3863 and sleeve nut according to DIN 3870.

Ensures correct mating of external circuit piping and hoses to the circulation pump.

Source
“Pump connection M38x1,5 male”
Operation

The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s.

Limits the choice of heat transfer fluid and ensures pump performance and safe operation.

Source
“max. permissible kin. viscosity 100 mm²/s”
Safety

The maximum system pressure is 6 bar, so the external circuit and connected components must be rated accordingly.

Prevents overpressure of the unit and connected external circuit.

Source
“max. System pressure 6 bar”
Installation

The unit has protection degree IP20 and must be operated in ambient temperatures between 5 °C and 40 °C.

Defines environmental limits and protection against ingress, affecting installation location.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The unit requires minimum filling capacity of 8.9 l and has an expansion tank filling capacity of 19.9 l.

Needed to size the external circuit volume and ensure sufficient heat transfer fluid.

Source
“min. filling capacity 8,9 l Filling capacity expansion tank 19,9 l”
Compliance

Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but combinations such as -5% voltage and +2% frequency are not allowed.

Ensures the electrical supply stays within safe operating limits and avoids invalid tolerance combinations.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation

Three-phase devices with current consumption less than 63 A are supplied with cable but without plug.

The installer must provide a suitable plug or direct connection for the three-phase supply.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety

The refrigerant is R-744 (A1, H280) with GWP 1 and UN number UN 2857, so refrigerant safety and transport classifications apply.

Affects safety measures, labeling, and handling of the refrigerant during installation and service.

Source
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280) Global Warming Potential (GWP) 1 UN-number UN 2857”
Operation

The circulation pump delivers 201 l/min maximum and 5.3 bar maximum delivery pressure, with reduced flow at higher pressure.

Used to verify that the external circuit pressure drop and required flow are within pump capability.

Source
“max. delivery 201 l/min max. delivery pressure 5,3 bar”
Maintenance

The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so suitable cooling water must be used.

Prevents corrosion and scaling in the cooling water circuit and maintains heat transfer performance.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”