Unistat P625w Technical Data

Contents

  1. Overview p. 1
    Product introduction and general description of Unistat P625w
  2. Spec pp. 1-2
    Technical data according to DIN 12876 including performance parameters
  3. p. 2 table, 17 rows
  4. p. 1 table, 31 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity100 mm²/s
Cooling water connectionG3/4 male
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure6 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1771 mm
Power supply requirement400V 3~ 50Hz
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/24

** Please respect space requirements. See operating conditions at www.huber-online.com

Unistat P625w — Technical data according to DIN 12876

CharacteristicValue
Order-No.5017.0101.01
Operating temperature range-60...200 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power12 kW
Cooling power with Thermooil at 200°C16 kW
Cooling power with Thermooil at 100°C16 kW
Cooling power with Thermooil at 20°C16 kW
Cooling power with Ethanol at 0°C16 kW
Cooling power with Ethanol at -20°C15 kW
Cooling power with Ethanol at -40°C6,4 kW
Cooling power with Ethanol at -60°C1,7 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-452A (A1, H280)
Global Warming Potential (GWP)2141
Circulation pumpMK pump
max. delivery201 l/min
max. delivery pressure5,3 bar
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min

Engineering Facts

13 facts · every claim linked to a page
Installation

The unit requires a 400 V three-phase supply, so the site must provide a 3~ 50 Hz feed sized for the 12 kW heater and 16 kW cooling load.

Determines electrical infrastructure, cable sizing and whether the facility can support the unit at all.

Source
“Power supply requirement 400V 3~ 50Hz”
Installation

Cooling water must be supplied at 1–4 bar differential and no more than 6 bar, so the building cooling loop needs a pressure regulator or check.

Prevents damage to the water-cooled condenser and ensures rated cooling performance.

Source
“min. cooling water differential pressure 1 bar max. cooling water differential pressure 4 bar max. cooling water pressure 6 bar”
Installation

The unit is designed for cooling water intake between 5 °C and 20 °C, and pipes must be insulated if water can drop below the condensation point.

Defines the acceptable cooling water supply range and the need for condensation insulation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling capacity is rated at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential, so actual capacity will differ if site conditions deviate.

Allows correct comparison of quoted cooling power against real site conditions.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Installation

The pump connection is M38x1.5 male with a Y-shaped bore per DIN 3863, so mating hoses must use ball socket DIN 3863 and sleeve nut DIN 3870.

Ensures correct fittings are ordered and leak-free connections are made.

Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Operation

The pump delivers 201 l/min at zero head but only 42 l/min at 5 bar, so high-pressure-drop loops must be checked against the pump curve.

Confirms whether the circulation pump can overcome the pressure drop of the external circuit.

Source
“max. delivery 201 l/min max. delivery pressure 5,3 bar”
Safety

The refrigerant R-452A has GWP 2141 and is classified A1/H280, so leak detection and refrigerant handling procedures must account for a high-GWP, flammable-classified substance.

Affects environmental compliance, leak monitoring and service procedures.

Source
“Refrigerant (ASHRAE, GHS) R-452A (A1, H280) Global Warming Potential (GWP) 2141”
Operation

The unit is rated IP20 and must be operated between 5 °C and 40 °C ambient, so it cannot be installed in a washdown or hot environment.

Sets the environmental envelope for the installation location.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The unit is 918x963x1771 mm, so space and access for a machine of this footprint must be planned before delivery.

Determines room layout, door widths and lifting/rigging requirements.

Source
“Overall dimensions WxDxH ** 918x963x1771 mm”
Installation

Three-phase devices below 63 A are supplied with cable but without a plug, so the customer must provide a suitable plug and connection.

Avoids a missing-plug surprise at commissioning and clarifies scope of supply.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Compliance

Voltage and frequency tolerances are ±5% and ±2% respectively, but the combination of -5% voltage with +2% frequency is not allowed.

Prevents operation outside the permitted supply envelope that could damage the compressor or electronics.

Source
“-5% voltage and +2% frequency -> not allowed!”
Operation

The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s, so fluid selection must respect this limit at operating temperature.

Guides selection of a suitable heat transfer fluid and avoids pump overload.

Source
“max. permissible kin. viscosity 100 mm²/s”
Maintenance

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Prevents corrosion and fouling that would degrade cooling performance.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”