Unistat P950w Technical Data Sheet

Contents

  1. Overview p. 1
    Introduces the Unistat P950w unit and its main features
  2. Spec p. 2
    Lists technical data according to DIN 12876 standard
  3. p. 2 table, 19 rows
  4. p. 1 table, 31 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 2,5 bar173 l/min
Delivery at 3,0 bar153 l/min
Delivery at 4,0 bar103 l/min
Delivery at 4,5 bar68 l/min
Pump connectionflange DN40 PN10/40 EN1092-1
max. permissible kin. viscosity100 mm²/s
Cooling water connectionG1 1/4 male
Consumption at water 15°C, flow 0°C5000 l/h
min. cooling water differential pressure3 bar
max. cooling water pressure6 bar
min. filling capacity30 l
Filling capacity expansion tank90 l
Overall dimensions WxDxH **2630x1300x1980 mm
Power supply requirement400V 3~ 50Hz
Pressure equipment categoryIV
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/23

** Please respect space requirements. See operating conditions at www.huber-online.com

Unistat P950w — Technical data according to DIN 12876

ParameterValue
Order-No.1065.0005.01
Operating temperature range-90...200 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power36 kW
Cooling power with Thermooil at 200°C36 kW
Cooling power with Thermooil at 100°C36 kW
Cooling power with Thermooil at 20°C36 kW
Cooling power with Ethanol at 0°C36 kW
Cooling power with Ethanol at -20°C36 kW
Cooling power with Ethanol at -40°C36 kW
Cooling power with Ethanol at -60°C25 kW
Cooling power with Ethanol at -80°C10 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-507 (A1, H280)
Global Warming Potential (GWP)3985
Refrigerant 2nd stage (ASHRAE, GHS)R-23 (A1, H280)
Global Warming Potential (GWP)14800
Refrigerant quantity 2nd stage7 kg
CO2 equivalent 2nd stage103,6 t
Circulation pump:MK pump
max. delivery260 l/min
max. delivery pressure4,8 bar

Engineering Facts

14 facts · every claim linked to a page
Installation

The unit requires a 400 V three-phase 50 Hz supply, so the electrical installation must be sized for a high-power three-phase load.

Determines the site power distribution, cable sizing and protection device selection before installation.

Source
“Power supply requirement 400V 3~ 50Hz”
Installation

The cooling water circuit must be supplied at 3–6 bar with a minimum differential pressure of 3 bar, so the site cooling water system must be verified before commissioning.

Insufficient cooling water pressure will prevent the water-cooled refrigeration machine from operating correctly.

Source
“min. cooling water differential pressure 3 bar max. cooling water pressure 6 bar”
Installation

The unit is designed for cooling water intake between 5 °C and 20 °C, and cooling water pipes must be insulated if the water temperature can fall below the condensation point.

Cooling water outside this range reduces cooling capacity and can cause condensation and electrical risk.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power drops significantly at low temperatures, from 36 kW at -40 °C to 25 kW at -60 °C and 10 kW at -80 °C, so the process heat load must be checked against the actual operating temperature.

Sizing only on the 36 kW headline figure will under-estimate the required capacity at deep cooling temperatures.

Source
“at -60°C 25 kW at -80°C 10 kW”
Installation

The pump connections are DN40 PN10/40 flanges, so the customer pipework must be prepared with matching flanges.

Mismatched flanges will prevent connection and may require adapters or rework of the piping.

Source
“Pump connection flange DN40 PN10/40 EN1092-1”
Installation

The unit requires a minimum filling capacity of 30 l and has a 90 l expansion tank, so the heat transfer fluid volume and expansion allowance must be planned.

Under-filling or insufficient expansion volume can cause pump cavitation and poor temperature control.

Source
“min. filling capacity 30 l Filling capacity expansion tank 90 l”
Safety

The leakage current exceeds 3.5 mA, so protective earthing and residual current device selection must account for this.

Standard 30 mA RCDs may nuisance-trip; earth connection and RCD type must be chosen accordingly.

Source
“Attention: leakage current > 3,5mA”
Compliance

Voltage and frequency tolerances are ±5 % and ±2 % respectively, but the combination of -5 % voltage with +2 % frequency is not allowed.

Site power quality must be checked; an out-of-tolerance supply can damage the compressor and electronics.

Source
“-5% voltage and +2% frequency -> not allowed!”
Installation

Three-phase devices drawing less than 63 A are delivered with cable but without a plug, so the customer must provide the final connection.

The electrical contractor must supply and install the appropriate plug or direct connection.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

The unit must be installed in an ambient temperature between 5 °C and 40 °C and has IP20 protection, so it must be kept in a dry indoor location.

IP20 offers no water protection, and ambient temperature outside the range affects performance and reliability.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Selection

The refrigerant charges are R-507 (GWP 3985) and R-23 (GWP 14800, 7 kg, 103.6 t CO2 equivalent), which affects F-gas compliance and leak monitoring obligations.

High-GWP refrigerants above the CO2-equivalent threshold trigger periodic leak checks and record-keeping.

Source
“Refrigerant quantity 2nd stage 7 kg CO2 equivalent 2nd stage 103,6 t”
Operation

The pump delivers 260 l/min at maximum with 4.8 bar maximum delivery pressure, and flow falls as pressure rises, so the external circuit pressure drop must be matched to the pump curve.

A circuit with high pressure drop may not achieve the required flow, affecting heat transfer and control stability.

Source
“max. delivery 260 l/min max. delivery pressure 4,8 bar”
Selection

The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s, which limits the choice of fluid at low temperatures.

Using a fluid that is too viscous at the operating temperature can overload the pump and reduce flow.

Source
“max. permissible kin. viscosity 100 mm²/s”
Installation

The unit measures 2630 x 1300 x 1980 mm, so sufficient floor space and access must be reserved for installation and maintenance.

Space must be planned for rigging, service access and ventilation around the unit.

Source
“Overall dimensions WxDxH ** 2630x1300x1980 mm”