Selection
The unit uses flammable refrigerant R-290 (A3, H220), so the installation must respect flammable-refrigerant safety requirements.
Determines ventilation, ignition-source and room-volume requirements at the installation site.
Source
“R-290 (A3, H220)”
Selection
Cooling capacity falls from 0.3 kW at 15 °C to 0.07 kW at -20 °C, so the load must be checked at the lowest operating temperature.
Sizing on the 15 °C figure would undersize the chiller for low-temperature duty.
Source
“at 15°C 0,3 kW at 0°C 0,2 kW at -10°C 0,14 kW at -20°C 0,07 kW”
Performance
Rated output data are valid only at 20 °C room temperature and cooling capacity may drop at higher ambient.
Prevents overestimating available cooling in a warm plant room.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
The supply must stay within ±5 % voltage and ±2 % frequency, and the combination of -5 % voltage with +2 % frequency is not permitted.
Defines the acceptable power quality at the connection point.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
Single/two-phase devices are delivered with a country-specific plug that must be specified at ordering.
Avoids a missing or wrong plug on delivery.
Source
“with power cable and country-specific plug (please specify when ordering)”
Installation
The pump connection is M16x1 male, and hose connector NW12 and M16x1 sleeve nuts are included.
Lets the piping be prepared to match the supplied fittings.
Source
“hose connector NW12 #6087, sleeve nuts thread M16x1#6089”
Operation
The plastic pump is not resistant to acetone and polyglycols, so these media must not be used without a more resistant pump.
Prevents chemical attack and pump failure with incompatible heat-transfer fluids.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection water should be mixed with glysantine or ethylene glycol rather than used pure.
Defines the correct heat-transfer fluid preparation for sub-zero operation.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation
The unit is IP20 and needs an ambient temperature between 5 °C and 40 °C.
Rules out wet, dusty or freezing locations and hot rooms.
Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation
The minimum fuse is 10 A and the maximum fuse is 16 A at 2.8 A max current.
Sets the upstream protection rating for the supply circuit.
Source
“min. Fuse 10A max. Fuse 16A”
Maintenance
The refrigerant charge is only 0.041 kg with GWP 0.02, giving a CO2 equivalent of 0.0 t.
Simplifies leak-check and F-gas documentation obligations.
Source
“Refrigerant quantity 0,041 kg”
Compliance
The equipment is EMC Class A, Group 1, so it is intended for industrial, not residential, environments.
Affects where the chiller may be installed regarding emitted interference.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Selection
The optional Pt100 sensor input only displays the process temperature and does not control it.
Prevents specifying it as a process-temperature control loop.
Source
“to display (not control) e.g. of the process temperature”