Selection
The unit's cooling capacity drops as ambient temperature rises, so size the chiller for the actual room temperature at the installation site.
Cooling capacity is rated at 20 °C ambient; higher ambient reduces available cooling and may require a larger model.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
The chiller must be installed where ambient temperature stays between 5 °C and 40 °C.
Operating outside the ambient range risks poor performance or equipment damage.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Installation
The unit requires a 110–120 V single-phase 60 Hz supply with a 16 A fuse, so verify site power and breaker rating before installation.
Mismatched voltage/frequency or undersized fusing prevents safe commissioning.
Source
“Power supply requirement
110-120V 1~ 60Hz
max. current
8,5 A
Fuse
16 A”
Safety
The refrigerant is R-290 (propane, A3 flammable), so ignition sources and ventilation must be considered at the installation location.
A3 flammable refrigerant imposes site safety and ventilation requirements.
Source
“Refrigerant (ASHRAE, GHS)
R-290 (A3, H220)”
Safety
The plastic pump is not resistant to acetone or polyglycols, so these fluids must not be used as the heat transfer medium.
Using incompatible fluids will damage the pump and void reliable operation.
Source
“Special Case: Acetone and Polyglycol: The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection, use water mixed with glysantine or ethylene glycol rather than pure water.
Correct fluid mixture prevents freezing and protects the cooling circuit at sub-zero temperatures.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation
The pump connections are M16x1 male, and hose connection NW12 with M16x1 sleeve nuts are included, so plan matching plumbing.
Knowing the connection thread ensures correct hoses and fittings are ordered.
Source
“Pump connection
M16x1 male”
Installation
The minimum filling capacity is 2.8 l and expansion volume is 2.2 l, so the external loop and fluid charge must be planned accordingly.
Underfilling or oversized external loops can cause cavitation or overflow.
Source
“min. filling capacity
2,8 l
Volume of expansion
2,2 l”
Performance
The pressure-suction pump delivers up to 24 l/min at 0.7 bar pressure and 18 l/min at 0.4 bar suction, which bounds external circuit resistance.
External piping pressure drop must stay within these pump limits for adequate flow.
Source
“max. delivery
24 l/min
max. delivery pressure
0,7 bar
max. delivery (suction)
18 l/min
max. delivery pressure (suction)
0,4 bar”
Operation
The permissible return-line temperature is 80 °C, which limits the heat load that can be returned to the chiller.
Exceeding return temperature can damage the unit or trip protection.
Source
“*** Permissible temperature in return line 80 °C”
Cumplimiento
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Site power quality must meet these combined tolerances for warranty and safe operation.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
The unit has IP20 protection, so it must be installed in a dry indoor location protected from water ingress.
IP20 is not water-resistant; outdoor or washdown locations are unsuitable.
Source
“Degree of Protection
IP20”
Selection
The unit is classified as Class A, Group 1 for electromagnetic disturbance, which affects placement near sensitive equipment.
Class A equipment may require EMC precautions when installed near sensitive electronics.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation
Single/two-phase devices are supplied with a country-specific plug that must be specified at ordering.
Failure to specify the plug type delays commissioning or requires field rework.
Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”