Selection
The chiller is rated for an operating temperature range of -10 to 100 °C, so the process must stay within these limits.
Defines the usable temperature window for the application and excludes processes outside it.
Source
“Operating temperature range
-10...100 °C”
Performance
Cooling capacity drops from 16 kW at 15 °C to 4 kW at -10 °C, so low-temperature duty requires a much larger unit or lower heat load.
Cooling capacity must be selected at the actual operating temperature, not at a nominal point.
Source
“at 15°C
16 kW
at 0°C
8,8 kW
at -10°C
4 kW”
Installation
The unit requires a 400 V three-phase 50 Hz supply, so the electrical installation must provide this service.
Determines the site power distribution, cable sizing and whether a three-phase feed is available.
Source
“Power supply (3 Phase)
400V 3~ 50Hz”
Installation
Three-phase devices below 63 A are delivered with cable but without a plug, so the customer must provide the final connection.
Affects installation planning and the need for a suitable disconnector or plug at site.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
The pump connection is G1 1/4 male, so hoses and adapters must match this thread.
Prevents mismatch of process connections and ensures correct hose coupling selection.
Source
“Pump connection
G1 1/4 male”
Operation
The unit is intended for externally closed applications, so an open process circuit is not permitted.
Defines the hydraulic circuit type and avoids incorrect use with open baths or tanks.
Source
“For externally closed applications.”
Operation
Ambient temperature must stay between 5 °C and 40 °C, and cooling capacity may fall above 20 °C.
Site conditions outside this range can reduce performance or prevent safe operation.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Performance
Cooling capacity is valid at 20 °C room temperature and may drop if ambient temperature rises.
Prevents overestimating capacity in warm plant rooms and supports proper derating.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Cumplimiento
Voltage and frequency tolerances are ±5 % and ±2 % respectively, but not all combinations are allowed.
Ensures the site supply quality is checked before installation to avoid invalid operating conditions.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Cumplimiento
The equipment is EMC class A group 1, so it may cause radio interference in residential areas.
Affects installation location and the need for EMC measures in sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Safety
The refrigerant is R-449A with GHS hazard H280, so refrigerant handling and ventilation must be considered.
Informs risk assessment for refrigerant leakage and service access.
Source
“R-449A (A1, H280)”
Maintenance
The minimum filling capacity is 14 l and expansion volume is 39 l, so the external circuit volume must be checked.
Prevents underfilling or overflow and supports correct heat-transfer fluid charge.
Source
“min. filling capacity
14 l
Volume of expansion
39 l”
Installation
The unit has IP20 protection, so it must be installed in a dry indoor location.
Excludes wet or dusty environments and guides enclosure or room requirements.
Source
“Degree of Protection
IP20”
Selection
The pump delivers 99 l/min maximum and 39 l/min at 5.0 bar, so system pressure drop must be matched.
Ensures the circulation pump can overcome the external circuit resistance at the required flow.
Source
“max. delivery
99 l/min
max. delivery pressure
5,9 bar”