Installation
The chiller requires a three-phase 400 V supply, so the site must provide a suitable 3-phase power connection.
Determines electrical infrastructure and whether a 3-phase feed is available at the installation point.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation
The unit is rated IP20, so it must be installed in a dry indoor location protected from water and dust ingress.
Affects placement and enclosure requirements to avoid moisture/dust damage.
Source
“Degree of Protection IP20”
Installation
Ambient temperature must stay between 5 °C and 40 °C for reliable operation.
Room conditions must be checked during site selection to avoid derating or faults.
Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation
Cooling water supply must be between 5 °C and 20 °C inlet temperature, and pipes must be insulated if below the condensation point.
Cooling water temperature directly affects cooling capacity and condensation risk.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
Cooling water differential pressure must be at least 1 bar and must not exceed 6 bar.
Ensures adequate flow without overpressurizing the water circuit.
Source
“min. cooling water differential pressure 1 bar max. cooling water pressure 6 bar”
Performance
Cooling capacity drops as water temperature decreases, from 30 kW at 15 °C to 8 kW at -20 °C.
Needed to verify the chiller can handle the process heat load at the required setpoint.
Source
“at 15°C 30 kW at 0°C 18 kW at -10°C 13 kW at -20°C 8 kW”
Performance
The circulation pump delivers 210 l/min max and 202 l/min at 1.1 bar, with pressure-dependent flow decline.
Must be matched to the external circuit pressure drop to ensure adequate flow.
Source
“max. delivery 210 l/min”
Installation
Pump and cooling water connections are G1 1/4 male and G3/4 male respectively, so matching fittings are required.
Determines hose/pipe adapters needed for commissioning.
Source
“Pump connection G1 1/4 male Cooling water connection G3/4 male”
Operation
The unit uses R-449A refrigerant with GWP 1397, which has environmental reporting implications.
Affects refrigerant handling, leak reporting, and environmental compliance.
Source
“R-449A (A1, H280) Global Warming Potential (GWP) 1397”
Cumplimiento
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Power quality must be verified to avoid voiding warranty or causing malfunction.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
Three-phase devices under 63 A are supplied with cable but without a plug, so a suitable plug must be provided on site.
Affects electrical installation planning and commissioning.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
The unit has adjustable overtemperature protection according to DIN 12876, which must be set for the application.
Critical for protecting the process and preventing overheating.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Maintenance
Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality should be used.
Prevents corrosion and fouling that could reduce cooling performance.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”