Unichiller P022 OLÉ — Technical Datasheet

Contenido

  1. Overview p. 1
    Product introduction and general description of the chiller unit
  2. Spec pp. 1-2
    Technical data, performance figures and operating parameters per DIN 12876
  3. p. 2 table, 2 rows
  4. p. 1 table, 40 rows

Technical data according to DIN 12876

ParameterValue
max. ambient temperature40 °C
from Serial-No.:S439735

Unichiller P022 OLÉ — Technical data according to DIN 12876

ParameterValue
Order-No.3010.0139.98
Operating temperature range-10...40 °C
temperature set point / displaydigital
Internal temperature sensorPt100
Resolution of display0,1 K
Interface digitalUSB (Device), RS232
Interface
Temperature stability at -10°C0,5 K
Alarm messageoptic, acoustic
Safety classificationI / NFL
Cooling power at 15°C2,2 kW
Cooling power at 0°C1,6 kW
Cooling power at -10°C1 kW
Refrigeration machineair-cooled, natural
refrigerant
Refrigerant (ASHRAE, GHS)R-290 (A3, H220)
Global Warming Potential (GWP)0,02
Refrigerant quantity0,24 kg
CO2 equivalent0,0 t
UN-numberUN 3358
Circulation pumpB
at 0,5 bar21 l/min
at 1,0 bar17 l/min
at 1,5 bar11 l/min
at 2,0 bar6 l/min
max. delivery25 l/min
max. delivery pressure2,5 bar
Pump connectionG3/4 male
min. filling capacity3,8 l
expansion tank1,7 l
Overall dimensions WxDxH **460x590x743 mm
Net weight81 kg
sound pressure level +/- 4 dB(A)65 dB(A)
Power supply requirement220-240V 1~ 50Hz
max. current9 A
min. Fuse10A
max. Fuse16A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C

** Overall dimensions WxDxH

Engineering Facts

14 facts · every claim linked to a page
Selection

The chiller is rated for an operating temperature range of -10 to 40 °C, so process requirements outside this window cannot be met.

Defines the process temperature envelope for which the unit can be selected.

Source
“Operating temperature range -10...40 °C”
Safety

The refrigerant is R-290 (A3, H220), a flammable natural refrigerant, which affects site safety classification and handling requirements.

Flammable refrigerant classification drives installation ventilation and safety measures.

Source
“R-290 (A3, H220)”
Installation

The unit requires a 220-240 V single-phase 50 Hz supply with a minimum 10 A fuse, so the electrical circuit must be sized accordingly.

Determines the electrical supply and protection device needed at the installation site.

Source
“Power supply requirement 220-240V 1~ 50Hz”
Installation

The pump connection is G3/4 male, so mating hoses and couplings must match this thread.

Ensures correct hydraulic connection hardware is ordered and installed.

Source
“Pump connection G3/4 male”
Performance

Cooling capacity drops from 2.2 kW at 15 °C to 1 kW at -10 °C, so capacity must be checked at the actual operating temperature.

Prevents oversizing or undersizing based on a single nominal capacity figure.

Source
“at 15°C 2,2 kW at 0°C 1,6 kW at -10°C 1 kW”
Performance

The circulation pump delivers 21 l/min at 0.5 bar but only 6 l/min at 2.0 bar, so system pressure drop must be matched to the pump curve.

Flow at the actual system backpressure determines whether the pump is adequate.

Source
“at 0,5 bar 21 l/min at 1,0 bar 17 l/min at 1,5 bar 11 l/min at 2,0 bar 6 l/min”
Installation

The minimum filling capacity is 3.8 l and the expansion tank is 1.7 l, so the loop volume and expansion allowance must be planned.

Ensures the circuit has sufficient fluid volume and expansion capacity.

Source
“min. filling capacity 3,8 l expansion tank 1,7 l”
Installation

The unit has IP20 protection, so it must be installed in a dry indoor location protected from water ingress.

Restricts installation environment and prevents moisture-related failures.

Source
“Degree of Protection IP20”
Operation

The minimum ambient temperature is 5 °C and the maximum is 40 °C, so the installation room must stay within this range.

Ambient conditions outside this range affect reliable operation and cooling performance.

Source
“min. ambient temperature 5 °C”
Performance

Cooling capacity data are valid at 20 °C room temperature and may drop if ambient temperature rises, so site conditions must be considered.

Prevents expecting nominal capacity in a warmer installation room.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Cumplimiento

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.

Defines acceptable supply quality for warranty and reliable operation.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Operation

The plastic pump is not resistant to acetone and polyglycols, so these fluids must be avoided or a more resistant pump specified.

Prevents chemical attack and premature pump failure from incompatible heat transfer fluids.

Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation

For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.

Guides correct heat transfer fluid preparation to avoid freezing damage.

Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation

Single-phase devices are supplied with a power cable and country-specific plug that must be specified at ordering.

Ensures the correct plug type is delivered for the installation country.

Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”