Unistat 640w Technical Data

Contenido

  1. Overview p. 1
    Product introduction and general description of the Unistat 640w unit
  2. Spec pp. 1-2
    Technical performance data and operating parameters per DIN 12876
  3. p. 2 table, 18 rows
  4. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
max. permissible kin. viscosity100 mm²/s
Cooling water connectionG3/4 male
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure6 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1772 mm
Net weight728 kg
Power supply requirement400V 3~ 50Hz
max. current48 A
Fuse3x50A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S584714

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unistat 640w (Order-No.: 5020.0100.01)

ParameterValue
Operating temperature range-60...200 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power24 kW
Cooling power with Thermooil at 200°C32 kW
Cooling power with Thermooil at 100°C32 kW
Cooling power with Thermooil at 20°C35 kW
Cooling power with Ethanol at 0°C35 kW
Cooling power with Ethanol at -20°C30 kW
Cooling power with Ethanol at -40°C14 kW
Cooling power with Ethanol at -60°C3,5 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-452A (A1, H280)
Global Warming Potential (GWP)2141
Refrigerant quantity5,5 kg
CO2 equivalent11,8 t
Circulation pump:MK pump
max. delivery196 l/min
max. delivery pressure2,5 bar
Delivery at 0,5 bar175 l/min
Delivery at 1,0 bar152 l/min
Delivery at 1,5 bar123 l/min
Delivery at 2,0 bar86 l/min
Pump connectionM38x1,5 male

Таблица приведена в исходном виде (характеристика — значение); транспонирование не требуется, так как это не матрица конфигураций.

Engineering Facts

13 facts · every claim linked to a page
Installation

The unit requires a 400 V three-phase supply with a maximum current of 48 A and 3x50 A fusing, so the electrical installation must be sized accordingly.

Determines the site power distribution, cable cross-section and breaker rating needed before installation.

Source
“Power supply requirement 400V 3~ 50Hz max. current 48 A Fuse 3x50A”
Installation

The cooling water circuit must be supplied at 1–4 bar differential pressure and no more than 6 bar, with G3/4 male connections.

Defines the required cooling water supply pressure and connection size for proper heat rejection.

Source
“min. cooling water differential pressure 1 bar max. cooling water differential pressure 4 bar max. cooling water pressure 6 bar”
Operation

Cooling water inlet must be between 5 °C and 20 °C; lower temperatures require insulating the cooling water pipes to prevent condensation.

Specifies the allowable cooling water temperature window and the condensation risk mitigation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Rated cooling power is valid only at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure; higher cooling water temperature reduces cooling power.

Prevents overestimating cooling capacity if site conditions differ from the rating basis.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and - outlet.”
Cumplimiento

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and the combination of -5% voltage with +2% frequency is not allowed.

Ensures the supply quality is checked against EN60034-1 before commissioning.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety

Leakage current exceeds 3.5 mA, so protective earthing and RCD selection must account for this.

Affects earth connection and residual current device selection for safe operation.

Source
“Attention: leakage current > 3,5mA”
Installation

Three-phase devices below 63 A are delivered with cable but without a plug, so a suitable plug must be provided on site.

Avoids delays at commissioning because the mating plug is not included.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

The unit is IP20 and must be installed where ambient temperature stays between 5 °C and 40 °C.

Constrains the installation location regarding dust/water ingress and room climate.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Selection

The refrigerant R-452A has a GWP of 2141 and a charge of 5.5 kg, giving 11.8 t CO2 equivalent that must be considered for environmental compliance.

Relevant for F-gas reporting and environmental permitting at the installation site.

Source
“Global Warming Potential (GWP) 2141 Refrigerant quantity 5,5 kg CO2 equivalent 11,8 t”
Installation

The unit is water-cooled and CFC/HCFC-free, so a cooling water circuit with compatible materials (copper, stainless steel 1.4401, MS, PA, PPE, PTFE, EPDM) is required.

Confirms the need for a cooling water supply and compatible wetted materials.

Source
“Refrigeration machine water-cooled, CFC- and HCFC-free”
Operation

The pump delivers 196 l/min maximum and 175 l/min at 0.5 bar, with M38x1.5 male connections, so external circuit pressure drop must be checked.

Allows verification that the external loop resistance matches the available pump curve.

Source
“max. delivery 196 l/min max. delivery pressure 2,5 bar Delivery at 0,5 bar 175 l/min”
Maintenance

Minimum filling capacity is 8.9 l and the expansion tank holds 19.9 l, so the heat transfer fluid volume must be planned accordingly.

Determines the required heat transfer fluid quantity and expansion volume for the system.

Source
“min. filling capacity 8,9 l Filling capacity expansion tank 19,9 l”
Installation

The unit weighs 728 kg and measures 918x963x1772 mm, so floor loading and access clearance must be verified.

Needed for transport planning, floor loading and space requirements at the installation site.

Source
“Overall dimensions WxDxH ** 918x963x1772 mm Net weight 728 kg”