Engineering Facts
13 facts · every claim linked to a page
Installation
The unit requires cooling water with a minimum differential pressure of 3 bar and a maximum pressure of 6 bar, so the site water supply must be verified before installation.
Insufficient differential pressure will prevent rated cooling performance, while overpressure can damage the cooling circuit.
Source
“min. cooling water differential pressure
3 bar
max. cooling water pressure
6 bar”
Installation
The cooling water inlet temperature must be kept between 5 °C and 20 °C, and if it can drop below the condensation point the cooling water pipes inside the unit must be insulated.
Operating outside this range or without insulation risks condensation, corrosion and reduced cooling capacity.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Rated cooling power is only valid at 20 °C room temperature, 15 °C cooling water inlet and 3 bar differential pressure, so actual capacity will differ at other site conditions.
Selection must account for derating when the available cooling water is warmer or the differential pressure is lower than the rating basis.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 3 bar differential pressure between cooling water inlet and -
outlet.”
Safety
The refrigerant is R-290 (propane, A3, H220), a flammable natural refrigerant, which affects the safety classification and handling requirements.
Flammable refrigerant classification influences installation clearances, ignition-source restrictions and service procedures.
Source
“R-290 (A3, H220)”
Operation
The plastic pump is not resistant to acetone or polyglycols, so these media must not be used in the circuit.
Using incompatible media will damage the pump; a more resistant plastic is only available on request at extra cost.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on other additives.
Correct freeze protection prevents ice formation and damage when operating near or below 0 °C.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation
The electrical supply must be 208–240 V single or two-phase at 50/60 Hz with a minimum 10 A and maximum 16 A fuse.
The site power and protection device must match these limits to avoid nuisance tripping or inadequate protection.
Source
“208-240V 1~/2~ 50/60Hz
max. current
4 A
min. Fuse
10A
max. Fuse
16A”
Cumplimiento
Voltage and frequency tolerances must be applied simultaneously: ±5 % voltage with ±2 % frequency, and combinations such as -5 % voltage with +2 % frequency are not allowed.
Supply quality outside the permitted combined tolerance can cause unreliable operation and is a compliance condition for installation.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The unit has IP20 protection and must be installed where ambient temperature stays between 5 °C and 40 °C.
IP20 offers no water protection and the ambient limits define the acceptable installation environment.
Source
“Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Operation
The return line may reach 80 °C, which is the permissible temperature limit for that connection.
Return-line temperature affects hose/pipe material selection and safe operation of the external circuit.
Source
“Permissible temperature in return line 80 °C”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water may be used.
Water chemistry must be compatible with these materials to avoid corrosion and fouling of the cooling circuit.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Selection
The Pt100 process sensor option only displays the process temperature and does not control it, and it must be ordered factory-fitted.
Specifying this option for control purposes would be a functional error; it must be decided at order time.
Source
“Option: Pt100 sensor connection #10519 to display (not control) e.g. of the process temperature (only available factory fitted, additional charge)”
Operation
Whisper mode reduces sound pressure to 51 dB(A) ±4 dB(A) but also reduces pump delivery to 14 l/min and 0.2 bar.
Noise-sensitive installations can use whisper mode, but the reduced pump performance must still meet the process flow requirement.