Introduces the Unichiller 025w-H OLÉ chiller model
Specp. 2
Lists technical data according to DIN 12876 standard
Engineering Facts
14 facts · every claim linked to a page
Installation
The unit requires cooling water with a minimum differential pressure of 1 bar and a maximum supply pressure of 6 bar at the G1/2 male connection.
Ensures the water supply circuit can deliver adequate flow without exceeding component pressure ratings.
Source
“min. cooling water differential pressure 1 bar”
Installation
Cooling water inlet temperature must be kept between 5°C and 20°C, and pipes must be insulated if condensation occurs.
Defines the permissible cooling water supply conditions and condensation protection needed for reliable operation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling capacity is rated at 2.5 kW at 15°C, 2 kW at 0°C, and 1.2 kW at -10°C, so capacity must be checked against the actual process load at the target temperature.
Cooling power drops significantly at lower temperatures, affecting selection for sub-ambient process cooling.
Source
“at 15°C 2,5 kW at 0°C 2 kW at -10°C 1,2 kW”
Installation
The electrical supply must be 220–240 V single-phase 50 Hz with a 16 A fuse and 15 A maximum current draw.
Determines the site power circuit, breaker sizing, and single-phase supply requirement.
Source
“Power supply requirement 220-240V 1~ 50Hz max. current 15 A Fuse 16 A”
Cumplimiento
Voltage tolerance is ±5% only when frequency tolerance is simultaneously ±2%, and opposite-sign deviations are not allowed.
Prevents installation on unstable mains where combined voltage and frequency deviations could damage the compressor or electronics.
Source
“-5% voltage and +2% frequency -> not allowed!”
Operation
The plastic pump is not resistant to acetone or polyglycols, so these fluids must be avoided or a more resistant pump specified.
Prevents chemical attack and premature pump failure when selecting heat transfer fluid.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.
Guides correct heat transfer fluid preparation for low-temperature operation.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Safety
The refrigerant R-449A is classified A1 with GHS hazard H280, and the charge is 0.4 kg corresponding to 0.6 t CO2 equivalent.
Informs refrigerant safety classification, leak handling, and F-gas reporting obligations.
Source
“R-449A (A1, H280)”
Installation
The unit is IP20 and must be installed in a dry, protected location away from water ingress.
Restricts installation environment and prevents moisture-related electrical hazards.
Source
“Degree of Protection IP20”
Operation
Ambient temperature must remain between 5°C and 40°C for specified performance.
Defines the room conditions required for reliable operation and rated cooling capacity.
Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so only compatible water quality should be used.
Prevents corrosion or scaling by matching water quality to wetted materials.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Selection
The pump delivers 21 l/min at 0.5 bar and up to 29 l/min maximum with 1 bar maximum delivery pressure.
Allows verification that circulation flow and pressure suit the external loop resistance.