Installation
The chiller requires a three-phase 400 V supply with a 3x16 A fuse, so the electrical installation must be sized accordingly.
Determines the site power supply, cable and protection device rating before installation.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation
The unit is water-cooled and needs a cooling water supply with differential pressure between 0.5 and 6 bar.
Cooling water pressure must be verified on site to ensure adequate flow and avoid overpressure damage.
Source
“min. cooling water differential pressure 0,5 bar”
Installation
Cooling water inlet temperature must be kept between 5 °C and 20 °C for the published performance data to apply.
Defines the permissible cooling water supply conditions and warns that higher temperatures reduce cooling capacity.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water temperature can fall below the dew point, the cooling water pipes inside the unit must be insulated.
Prevents condensation and corrosion inside the unit when cold cooling water is used.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and material compatibility to avoid corrosion or fouling of the cooling circuit.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
Three-phase devices below 63 A are delivered with a cable but without a plug, so a suitable plug must be provided on site.
Affects electrical installation planning and the need to procure a matching plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation
The unit is rated for ambient temperatures from 5 °C to 40 °C, which limits where it can be installed.
Room conditions must be checked to keep the chiller within its operating envelope.
Source
“min. ambient temperature 5 °C”
Operation
The refrigerant is R-449A with GWP 1397 and a charge of 1.03 kg, giving a CO2 equivalent of 1.4 t.
Relevant for refrigerant handling, leak reporting and environmental compliance.
Source
“Refrigerant (ASHRAE, GHS) R-449A (A1, H280)”
Performance
Cooling capacity drops from 10 kW at 20 °C to 3.9 kW at -20 °C, so the required load must be checked at the lowest operating temperature.
Ensures the chiller can remove the process heat at the coldest set point, not just at ambient.
Source
“at -20°C 3,9 kW”
Performance
The circulation pump delivers 48 l/min at zero head but only 11 l/min at 3.0 bar, so system pressure drop must be matched to the pump curve.
Prevents undersized flow through the external circuit at high pressure drop.
Source
“Delivery at 3,0 bar 11 l/min”
Operation
The minimum filling capacity is 18 l and the expansion volume is 48 l, which sets the minimum heat transfer fluid charge.
Determines the required volume of heat transfer fluid and expansion tank sizing for safe operation.
Source
“min. filling capacity 18 l”
Cumplimiento
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Site power quality must be checked to avoid invalid supply combinations that could damage the unit.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety
The unit has safety classification III / FL and adjustable overtemperature protection according to DIN 12876.
Confirms the safety concept and the need to set the overtemperature limit for the application.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Installation
The unit has IP20 protection, so it must be installed in a dry indoor location protected from water ingress.
Restricts installation environment and prevents moisture or dust ingress hazards.
Source
“Degree of Protection IP20”