Contenido

  1. Overview p. 1
    Product name and general description of the chiller unit
  2. Spec pp. 1-2
    Technical data table according to DIN 12876
  3. p. 2 table, 3 rows
  4. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/19

Technical data according to DIN 12876

ParameterValue
Operating temperature range-20...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
Temperature stability at -10°C0,2 K
Safety classificationIII / FL
Heating power2 kW
Cooling power at 15°C18 kW
Cooling power at 0°C18 kW
Cooling power at -10°C11 kW
Cooling power at -20°C6 kW
Refrigeration machineair-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Circulation pump:D3
max. delivery210 l/min
max. delivery pressure4,7 bar
Delivery at 1,1 bar202 l/min
Delivery at 1,5 bar193 l/min
Delivery at 2,0 bar179 l/min
Delivery at 2,5 bar159 l/min
Delivery at 3,0 bar140 l/min
Delivery at 3,5 bar115 l/min
Delivery at 4,0 bar77 l/min
Delivery at 4,5 bar31 l/min
Pump connectionG1 1/4 male
min. filling capacity14 l
Volume of expansion39 l
Overall dimensions WxDxH **905x1582x1902 mm
Power supply (3 Phase)400V 3~ 50Hz
Pressure equipment categoryI
Degree of ProtectionIP20

** Overall dimensions WxDxH

Engineering Facts

14 facts · every claim linked to a page
Selection

The chiller delivers 18 kW cooling at 15 °C and 0 °C but only 6 kW at -20 °C, so sizing must be based on the lowest required operating temperature.

Cooling capacity collapses at low temperature; undersizing at -20 °C will cause loss of temperature control.

Source
“at 15°C 18 kW at 0°C 18 kW at -10°C 11 kW at -20°C 6 kW”
Selection

The unit uses R-449A with GWP 1397, which matters for refrigerant regulations and environmental compliance planning.

High-GWP refrigerant affects regulatory compliance, leak monitoring obligations and future serviceability.

Source
“R-449A (A1, H280) Global Warming Potential (GWP) 1397”
Installation

The chiller is air-cooled, so sufficient room ventilation and respect of space requirements are mandatory at the installation site.

Insufficient air flow around an air-cooled condenser reduces cooling capacity and can trip the refrigeration circuit.

Source
“Please respect space requirements. See operating conditions at www.huber-online.com”
Installation

The three-phase 400 V unit is supplied with cable but without a plug, so the customer must provide a suitable mains connection and protection.

Electrical installation planning must include a correctly rated plug, breaker and earthing by a qualified electrician.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Mains voltage and frequency tolerances are ±5 % and ±2 % but must not be combined in the unfavorable direction, so supply quality must be verified.

Out-of-tolerance supply can damage the compressor and electronics and void warranty claims.

Source
“-5% voltage and +2% frequency -> not allowed!”
Operation

Cooling capacity data are valid at 20 °C room temperature and drop as ambient temperature rises, so hot plant rooms reduce performance.

Actual available cooling must be derated for the real ambient temperature at the installation site.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Operation

The permitted ambient temperature range is 5 to 40 °C, which defines where the unit may be installed and operated.

Operating outside this range risks compressor damage and invalidates performance specifications.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Operation

The pump delivers 210 l/min at zero head but only 77 l/min at 4.0 bar, so the system pressure drop must be checked against the pump curve.

External circuit resistance determines real flow; a high-pressure-drop loop may starve the process of flow.

Source
“max. delivery 210 l/min max. delivery pressure 4,7 bar”
Installation

The pump connection is G1 1/4 male, so hoses and adapters must match this thread size.

Wrong fittings cause leaks and delays during commissioning; correct couplings should be ordered in advance.

Source
“Pump connection G1 1/4 male”
Operation

Minimum filling capacity is 14 l and expansion volume is 39 l, which sets the heat transfer fluid charge and expansion allowance.

Underfilling causes pump cavitation and poor control; the expansion volume limits the total loop volume.

Source
“min. filling capacity 14 l Volume of expansion 39 l”
Safety

The unit has adjustable overtemperature protection per DIN 12876 and safety classification III/FL, relevant for flammable or sensitive media.

Overtemperature protection must be set correctly for the fluid used to prevent fire or fluid degradation.

Source
“With adjustable overtemperature protection according to DIN 12876.”
Cumplimiento

The equipment is EMC class A group 1, so it is intended for industrial environments and may cause interference in residential areas.

Class A equipment may require additional filtering or separation from sensitive electronics in mixed environments.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

The unit is IP20, so it must be installed in a dry, dust-free location protected from water ingress.

IP20 offers no water protection; washdown or outdoor installation is not permissible.

Source
“Degree of Protection IP20”
Selection

The unit is intended for externally closed applications, which constrains the hydraulic circuit design.

Open-loop or tank-vented circuits are not supported and would cause fluid loss and control problems.

Source
“For externally closed applications.”