Installation
The chiller is water-cooled and requires a minimum cooling water differential pressure of 1 bar between inlet and outlet.
Ensures the cooling water supply can provide adequate flow through the condenser.
Source
“min. cooling water differential pressure 1 bar”
Installation
Cooling water intake temperature must be between 5°C and 20°C; below the condensation point the cooling water pipes in the unit must be insulated.
Defines the permissible cooling water supply conditions and insulation requirement to prevent condensation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
The maximum cooling water pressure is 6 bar.
Prevents overpressure damage to the cooling water circuit.
Source
“max. cooling water pressure 6 bar”
Installation
Three-phase devices with current consumption less than 63A are supplied with cable but without plug.
The installer must provide a suitable plug and connection for the 22 A three-phase supply.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and the combination of -5% voltage with +2% frequency is not allowed.
Defines acceptable supply quality for reliable operation of the 400V 3~ 50Hz unit.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Selection
Cooling power depends on flow temperature: 25 kW at 15°C, 18 kW at 0°C, 11 kW at -10°C and 6 kW at -20°C.
Allows sizing the chiller for the required heat load at the actual process temperature.
Source
“at 15°C 25 kW at 0°C 18 kW at -10°C 11 kW at -20°C 6 kW”
Selection
The circulation pump delivers 210 l/min maximum and 202 l/min at 1.1 bar, dropping to 31 l/min at 4.5 bar.
Needed to match pump flow and pressure to the external circuit resistance.
Source
“max. delivery 210 l/min”
Selection
The refrigerant is R-449A with GWP 1397 and a charge of 2.6 kg, corresponding to 3.6 t CO2 equivalent.
Relevant for refrigerant regulations, leak detection and environmental compliance.
Source
“R-449A (A1, H280)”
Operation
The unit is intended for externally closed applications.
The external circuit must be closed; open-loop applications are not supported.
Source
“For externally closed applications.”
Operation
The minimum filling capacity is 15 l and the expansion volume is 22 l.
Determines the minimum heat transfer fluid volume required for safe operation.
Source
“min. filling capacity 15 l”
Operation
Ambient temperature must be between 5°C and 40°C.
Defines the allowable installation room temperature range.
Source
“min. ambient temperature 5 °C”
Safety
The unit has safety classification I / NFL according to DIN 12876.
Indicates the safety category relevant for use with flammable or non-flammable fluids.
Source
“Safety classification I / NFL”
Cumplimiento
The equipment is classified Class A, Group 1 for electromagnetic disturbance to EN55011.
Class A equipment may require EMC precautions in residential or light-industrial environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Maintenance
The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so suitable cooling water must be used.
Guides water quality selection to avoid corrosion and fouling of the mixed-material cooling circuit.
Source
“Please use suitable cooling water.”