Selection
The chiller's cooling capacity drops as ambient temperature rises, so size the unit for the actual room conditions.
Prevents undersizing when the installation room is warmer than 20 °C.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
Three-phase units below 63 A are supplied with cable but no plug, so the installer must provide a suitable plug.
Affects electrical installation planning and required site materials.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances must be met simultaneously, so verify the site supply before commissioning.
Ensures the 400 V 3~ supply is within the allowed combined tolerance.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
The unit is IP20, so it must be installed in a dry indoor location protected from water and dust ingress.
Determines suitable installation environment and enclosure needs.
Source
“Degree of Protection
IP20”
Installation
The pump connection is G1 1/4 male, so matching hose couplings must be provided for the external circuit.
Needed to order correct fittings and hoses for the process loop.
Source
“Pump connection
G1 1/4 male”
Operation
The unit is intended only for externally closed applications, so an open process circuit is not permitted.
Prevents misuse with open tanks that could cause overflow or contamination.
Source
“For externally closed applications.”
Operation
Ambient temperature must stay between 5 °C and 40 °C for reliable operation.
Defines the allowable room conditions for warranty and performance.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Safety
The refrigerant R-449A is classified A1 with GHS hazard H280, so ventilation and safe handling procedures are required.
Informs site risk assessment and refrigerant handling requirements.
Source
“R-449A (A1, H280)”
Safety
The unit has adjustable overtemperature protection per DIN 12876, which must be set for the application.
Critical safety setting to protect the process and equipment from overheating.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Performance
Cooling capacity falls from 26 kW at 0 °C to 10 kW at -20 °C, so low-temperature duty needs careful sizing.
Prevents overestimating available capacity at the cold end of the range.
Source
“at -20°C
10 kW”
Performance
Pump delivery drops with rising pressure, from 202 l/min at 1.1 bar to 31 l/min at 4.5 bar.
Needed to check whether the external circuit's pressure drop is acceptable.
Source
“Delivery at 4,5 bar
31 l/min”
Cumplimiento
The equipment is Class A, Group 1 for EMC, so it may cause radio interference in residential environments.
Affects installation location and EMC precautions in sensitive areas.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Cumplimiento
The unit is compliant with US-SNAP for industrial process refrigeration, confirming its intended end-use.
Confirms regulatory suitability for industrial process cooling applications.
Source
“The US-SNAP end-use for this equipment is the industrial process refrigeration.”
Maintenance
The refrigerant has a GWP of 1397, so leak checks and refrigerant accounting are important.
Relevant for environmental compliance and service planning.
Source
“Global Warming Potential (GWP)
1397”