Product introduction and general description of the chiller unit
Specpp. 1-2
Technical data, performance figures and operating parameters per DIN 12876
p. 2table, 11 rows
p. 1table, 33 rows
Technical data according to DIN 12876
Parameter
Value
Volume of expansion
22 l
Overall dimensions WxDxH **
760x800x1615 mm
Net weight
387 kg
Power supply (3 Phase)
400V 3~ 50Hz
max. current (3 Phase)
19,5 A
Fuse (3 phase)
3x20A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S621010
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876 — Unichiller 350Tw-H (Order-No.: 3021.0012.01)
Parameter
Value
Operating temperature range
-20...100 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,2 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
III / FL
Heating power
2 kW
Cooling power at 15°C
35 kW
Cooling power at 0°C
25 kW
Cooling power at -10°C
16 kW
Cooling power at -20°C
10 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)
Global Warming Potential (GWP)
1397
Refrigerant quantity
3 kg
CO2 equivalent
4,2 t
Circulation pump
D3
max. delivery
210 l/min
max. delivery pressure
4,7 bar
Delivery at 1,1 bar
202 l/min
Delivery at 1,5 bar
193 l/min
Delivery at 2,0 bar
179 l/min
Delivery at 2,5 bar
159 l/min
Delivery at 3,0 bar
140 l/min
Delivery at 3,5 bar
115 l/min
Delivery at 4,0 bar
77 l/min
Delivery at 4,5 bar
31 l/min
Pump connection
G1 1/4 male
Cooling water connection
G3/4 male
min. cooling water differential pressure
1 bar
max. cooling water pressure
6 bar
min. filling capacity
15 l
Таблица приведена как напечатано (характеристика — значение); строки Cooling power и Delivery являются отдельными строками с указанием условий.
Engineering Facts
12 facts · every claim linked to a page
Installation
The chiller is water-cooled and requires a cooling water supply with a minimum differential pressure of 1 bar and a maximum pressure of 6 bar.
To size the cooling water circuit and ensure adequate flow and pressure for heat rejection.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit must be operated with cooling water intake temperature between 5°C and 20°C, and pipes must be insulated if below the condensation point.
To avoid condensation and ensure specified cooling performance; outside this range performance drops.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling power is rated at 35 kW at 15°C, 25 kW at 0°C, 16 kW at -10°C, and 10 kW at -20°C, valid for 20°C room and 15°C cooling water.
To select the chiller for the actual heat load at the required process temperature.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Installation
The unit requires a 3-phase 400V 50Hz supply with max current 19.5 A and 3x20A fuses; three-phase devices under 63A are supplied with cable but without plug.
To plan electrical supply, protection, and provide a suitable plug on site.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances are ±5% and ±2% respectively, but simultaneous opposite-sign deviations are not allowed.
To ensure the power quality at the installation site meets the unit's requirements.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
The refrigerant R-449A has a GHS classification H280 (pressurized gas) and a GWP of 1397 with 3 kg charge (4.2 t CO2 equivalent).
To assess refrigerant safety, environmental impact, and leak detection requirements.
Source
“R-449A (A1, H280)”
Operation
The pump delivers 210 l/min max at 4.7 bar; flow drops with pressure, e.g., 140 l/min at 3.0 bar and 77 l/min at 4.0 bar.
To verify the pump can overcome the external circuit pressure drop at the required flow.
Source
“max. delivery 210 l/min”
Installation
The unit has IP20 protection and must be installed in an environment between 5°C and 40°C ambient temperature.
To ensure the installation location meets environmental and electrical safety requirements.
Source
“Degree of Protection IP20”
Maintenance
The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so suitable water quality is required.
To avoid corrosion and fouling by using compatible cooling water.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
The unit requires a minimum filling capacity of 15 l and has a 22 l expansion volume.
To size the external circuit and ensure sufficient thermal fluid volume.
Source
“min. filling capacity 15 l”
Cumplimiento
The equipment is classified as Class A, Group 1 for electromagnetic disturbance per EN55011.
To assess EMC compatibility and potential need for filtering or separation from sensitive equipment.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Selection
The unit is for externally closed applications and has an atmospheric open expansion tank.
To ensure the chiller is suitable for the intended closed-loop process.