Induztr
Resumen técnico Visor de documentos Modelos relacionados

Unimotive 27w

Contenido

  1. Overview p. 1
    Product introduction and general description of the Unimotive 27w unit
  2. Spec p. 2
    Technical data according to DIN 12876 including performance and dimensions
  3. p. 2 table, 25 rows
  4. p. 1 table, 26 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity200 mm²/s
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 0°C1530 l/h
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure6 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **730x804x1738 mm
Net weight456 kg
Power supply requirement400V 3~ 50Hz
max. current57 A
Fuse3x63A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S549354

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterValue
Operating temperature range-45...95 °C
Temperature stability at -10°C0,05 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C35 kW
Cooling power with Water/ Glysantin 40/60 at 0°C25 kW
at -20°C14,5 kW
at -30°C6,5 kW
at -40°C2,6 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-452A (A1, H280)
Global Warming Potential (GWP)2141
Refrigerant quantity3,6 kg
CO2 equivalent7,7 t
Circulation pump:MK pump
max. delivery201 l/min
max. delivery pressure5,3 bar

Engineering Facts

12 facts · every claim linked to a page
Selection

The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so the heat transfer fluid must be selected accordingly.

Determines whether the unit suits the intended automotive test fluid and prevents corrosion or freezing issues.

Source
“constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C”
Installation

The cooling water intake must be between 5°C and 20°C, and pipes must be insulated if below the condensation point.

Cooling water outside this range reduces cooling power or causes condensation, affecting installation design.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

Cooling water differential pressure must be between 1 bar and 4 bar, with maximum cooling water pressure 6 bar.

Ensures the facility cooling water supply meets the unit's hydraulic requirements.

Source
“min. cooling water differential pressure 1 bar”
Installation

The unit requires a 400V 3~ 50Hz supply with max current 57 A and 3x63A fusing.

Electrical infrastructure and protection devices must be sized accordingly.

Source
“Power supply requirement 400V 3~ 50Hz”
Installation

Three-phase devices with current consumption less than 63A are delivered with cable but without plug.

The installer must provide a suitable plug or hard-wired connection.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety

Leakage current exceeds 3.5 mA, which affects residual current device selection and earthing requirements.

Standard 30 mA RCDs may nuisance-trip; appropriate protective measures must be planned.

Source
“Attention: leakage current > 3,5mA”
Operation

Voltage and frequency tolerances are ±5% and ±2% respectively, but certain combinations are not allowed.

Prevents operation outside permissible supply conditions that could damage the unit.

Source
“-5% voltage and +2% frequency -> not allowed!”
Installation

The unit has IP20 protection and must be installed in an environment between 5°C and 40°C ambient temperature.

IP20 offers no water protection, so the installation location must be dry and within ambient limits.

Source
“Degree of Protection IP20”
Selection

Cooling power drops significantly at lower temperatures, from 35 kW at 20°C to 2.6 kW at -40°C.

Process heat loads at low temperatures must be checked against the reduced cooling capacity.

Source
“at -40°C 2,6 kW”
Installation

The pump connection is M38x1.5 male and requires ball socket per DIN 3863 and sleeve nut per DIN 3870.

Correct mating fittings must be procured for leak-free connection.

Source
“Pump connection M38x1,5 male”
Operation

The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s.

Fluid selection must respect this limit to avoid pump overload.

Source
“max. permissible kin. viscosity 200 mm²/s”
Maintenance

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water may be used.

Incompatible water chemistry can cause corrosion or fouling of the cooling circuit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”