Unimotive GL 30w-XT

Contenido

  1. Overview p. 1
    Introduces the Unimotive GL 30w-XT unit and its main features
  2. Spec p. 2
    Lists technical data according to DIN 12876 standard
  3. p. 2 table, 25 rows
  4. p. 1 table, 27 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity200 mm²/s
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 0°C3100 l/h
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure12 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1771 mm
Net weight900 kg
Power supply requirement460V 3~ 60Hz
max. current62,5 A
Fuse3x63A
Pressure equipment categoryII
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/23

** Please respect space requirements. See operating conditions at www.huber-online.com

Unimotive GL 30w-XT — Technical data according to DIN 12876

ParameterValue
Order-No.5009.0004.01
Operating temperature range-45...150 °C
Temperature stability at -10°C0,05 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationI / NFL
Heating power24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C35 kW
Cooling power with Water/ Glysantin 40/60 at 0°C35 kW
at -20°C22 kW
at -30°C14 kW
at -40°C8,5 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
Refrigerant quantity9 kg
CO2 equivalent0,0 t
Circulation pump:MK pump
max. delivery201 l/min
max. delivery pressure5,3 bar

Engineering Facts

14 facts · every claim linked to a page
Selection

The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so the heat transfer fluid must be selected accordingly.

Determines compatible heat transfer fluid and achievable low-temperature range for automotive test applications.

Source
“constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C”
Installation

The cooling water inlet temperature must be between 5°C and 20°C, and pipes must be insulated if condensation occurs.

Cooling water supply conditions must be verified on site before installation to avoid condensation and performance loss.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

The cooling water circuit requires a differential pressure between 1 bar and 4 bar and a maximum pressure of 6 bar.

The facility cooling water system must be sized to provide adequate differential pressure without exceeding the maximum.

Source
“min. cooling water differential pressure 1 bar max. cooling water differential pressure 4 bar max. cooling water pressure 6 bar”
Installation

The unit requires a 460V 3~ 60Hz supply with a maximum current of 62.5 A and a 3x63A fuse.

Electrical supply and branch protection must be planned to match this rating before installation.

Source
“Power supply requirement 460V 3~ 60Hz max. current 62,5 A Fuse 3x63A”
Installation

External branch circuit protection according to UL 489 is required.

The installer must provide UL 489 listed branch protection to meet compliance.

Source
“External branch circuit protection according to UL 489 required.”
Installation

Three-phase devices with current consumption less than 63A are delivered with cable but without plug.

The site must supply and install a suitable plug or hard-wired connection.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.

Supply quality must be checked to avoid invalid voltage/frequency combinations that could damage the unit.

Source
“-5% voltage and +2% frequency -> not allowed!”
Operation

Cooling power drops as cooling water temperature rises, and cooling water flow rate may need to increase.

Performance at higher cooling water temperatures must be accounted for in process design.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Operation

The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s.

Fluid selection must respect this viscosity limit to ensure proper pump operation.

Source
“max. permissible kin. viscosity 200 mm²/s”
Safety

The unit has adjustable overtemperature protection according to DIN 12876.

Safety settings must be configured for the application to protect the process and equipment.

Source
“With adjustable overtemperature protection according to DIN 12876.”
Safety

The refrigerant is R-744 (A1, H280) with a GWP of 1 and a charge of 9 kg.

Refrigerant safety classification and charge affect handling, ventilation, and environmental compliance.

Source
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280)”
Maintenance

Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so suitable cooling water must be used.

Cooling water quality must be compatible with these materials to prevent corrosion and fouling.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Cumplimiento

The equipment is classified as EN55011 Class A, Group 1 for electromagnetic compatibility.

Class A equipment may require additional EMC measures in residential or sensitive environments.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Selection

The unit is IP20 rated and must operate in ambient temperatures between 5°C and 40°C.

Installation location must meet the ambient temperature range and protection degree requirements.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”