Contenido

  1. Overview p. 1
    Introduces the Unistat 950w unit and its main features
  2. Spec p. 2
    Lists technical data according to DIN 12876 standard
  3. p. 2 table, 20 rows
  4. p. 1 table, 32 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 2,0 bar167 l/min
Delivery at 3,0 bar115 l/min
Pump connectionflange DN40 PN10/40 EN1092-1
max. permissible kin. viscosity100 mm²/s
Cooling water connectionG1 1/4 male
Consumption at water 15°C, flow 0°C5000 l/h
min. cooling water differential pressure3 bar
max. cooling water pressure6 bar
min. filling capacity30 l
Filling capacity expansion tank90 l
Overall dimensions WxDxH **2630x1300x1980 mm
Net weight2147 kg
Power supply requirement400V 3~ 50Hz
max. current120 A
Fuse3x125A
Pressure equipment categoryIV
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S513334

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterValue
Operating temperature range-90...200 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power36 kW
Cooling power with Thermooil at 200°C36 kW
Cooling power with Thermooil at 100°C36 kW
Cooling power with Thermooil at 20°C36 kW
Cooling power with Ethanol at 0°C36 kW
Cooling power with Ethanol at -20°C36 kW
Cooling power with Ethanol at -40°C36 kW
Cooling power with Ethanol at -60°C25 kW
Cooling power with Ethanol at -80°C10 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-507 (A1, H280)
Global Warming Potential (GWP)3985
Refrigerant quantity19,5 kg
CO2 equivalent77,7 t
Refrigerant 2nd stage (ASHRAE, GHS)R-23 (A1, H280)
Global Warming Potential (GWP)14800
Refrigerant quantity 2nd stage7 kg
CO2 equivalent 2nd stage103,6 t
Circulation pump: MK pump max. delivery240 l/min
max. delivery pressure4 bar
Delivery at 1,0 bar207 l/min

Engineering Facts

14 facts · every claim linked to a page
Installation

The unit requires a 400 V 3-phase 50 Hz supply with a maximum current of 120 A and 3x125 A fusing, so the electrical infrastructure must be sized accordingly.

Determines the site power distribution, cable sizing and breaker rating needed before installation.

Source
“Power supply requirement 400V 3~ 50Hz max. current 120 A Fuse 3x125A”
Installation

The cooling water connection is G1 1/4 male and requires 5000 l/h at 15 °C with a minimum differential pressure of 3 bar and maximum pressure of 6 bar.

Defines the cooling water supply capacity and pressure limits that must be available at the installation site.

Source
“Consumption at water 15°C, flow 0°C 5000 l/h min. cooling water differential pressure 3 bar max. cooling water pressure 6 bar”
Operation

The unit is designed for cooling water intake between 5 °C and 20 °C, and cooling power drops as the cooling water temperature rises.

Cooling water temperature directly affects achievable cooling capacity and must be kept within this range.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

If cooling water temperature falls below the condensation point, the cooling water pipes in the unit must be insulated.

Prevents condensation and corrosion on the cooling water circuit at low intake temperatures.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Installation

The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and treatment to avoid corrosion or damage to the cooling circuit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Cumplimiento

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and combinations such as -5% voltage with +2% frequency are not allowed.

Defines acceptable supply quality; out-of-tolerance combinations can damage the unit or void compliance.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation

Three-phase devices drawing more than 63 A are supplied without cable and without plug, so the customer must provide the power connection.

Affects installation planning and cost since the power cable and plug are not included.

Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Safety

The unit has safety classification III / FL and adjustable overtemperature protection according to DIN 12876.

Indicates the safety category for flammable or non-flammable fluids and the required protective measures.

Source
“Safety classification III / FL”
Safety

The refrigerant R-507 has a GWP of 3985 with 19.5 kg charge (77.7 t CO2 equivalent), and the second stage R-23 has a GWP of 14800 with 7 kg charge (103.6 t CO2 equivalent).

Relevant for refrigerant regulations, leak monitoring and environmental compliance obligations.

Source
“Global Warming Potential (GWP) 3985 Refrigerant quantity 19,5 kg CO2 equivalent 77,7 t”
Installation

The unit has overall dimensions of 2630x1300x1980 mm and a net weight of 2147 kg, requiring adequate floor space and structural support.

Needed for site layout, transport route planning and floor loading assessment.

Source
“Overall dimensions WxDxH ** 2630x1300x1980 mm Net weight 2147 kg”
Operation

The ambient temperature must be between 5 °C and 40 °C, and the degree of protection is IP20.

Defines the permissible operating environment and limits on dust and water exposure.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The pump connection is a flange DN40 PN10/40 according to EN1092-1, and pipework must use ball socket per DIN 3863 and sleeve nut per DIN 3870.

Determines the mating flange and hose fittings required for connecting the external circuit.

Source
“Pump connection flange DN40 PN10/40 EN1092-1”
Performance

The circulation pump delivers a maximum of 240 l/min at 4 bar, with 207 l/min at 1.0 bar, 167 l/min at 2.0 bar and 115 l/min at 3.0 bar.

Used to verify that the external circuit pressure drop is compatible with the available pump curve.

Source
“max. delivery 240 l/min max. delivery pressure 4 bar”
Operation

The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s.

Limits the choice of heat transfer fluid, especially at low temperatures where viscosity rises.

Source
“max. permissible kin. viscosity 100 mm²/s”