Unistat P525w Technical Data

Contenido

  1. Overview p. 1
    Product introduction and general description of the Unistat P525w unit
  2. Spec p. 2
    Technical data according to DIN 12876 including performance and dimensions
  3. p. 2 table, 23 rows
  4. p. 1 table, 29 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 1,5 bar57 l/min
Delivery at 2,0 bar46 l/min
Delivery at 2,5 bar32 l/min
Pump connectionM30x1,5 male
max. permissible kin. viscosity50 mm²/s
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 20°C792 l/h
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity5,1 l
Filling capacity expansion tank18 l
Overall dimensions WxDxH **540x604x1332 mm
Net weight208 kg
sound pressure level +/- 4 dB(A)61 dB(A)
Power supply requirement400V 3~ 50Hz
max. current14 A
Fuse3x16A
max. current convertible (3 phase)13,5 A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.1/20

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unistat P525w (Order-No.: 1051.0004.01)

CharacteristicValue
Operating temperature range-55...250 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power6 kW
Cooling power with Thermooil at 250°C10 kW
Cooling power with Thermooil at 200°C10 kW
Cooling power with Thermooil at 100°C10 kW
Cooling power with Thermooil at 20°C10 kW
Cooling power with Ethanol at 0°C7 kW
Cooling power with Ethanol at -20°C4,2 kW
Cooling power with Ethanol at -40°C1,5 kW
Cooling power with Ethanol at -50°C0,65 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-452A (A1, H280)
Global Warming Potential (GWP)2141
Refrigerant quantity1,44 kg
CO2 equivalent3,1 t
Circulation pump: MK pump max. delivery82 l/min
Circulation pump: MK pump max. delivery pressure3 bar
Circulation pump: MK pump Delivery at 0,5 bar75 l/min
Circulation pump: MK pump Delivery at 1,0 bar66 l/min

Значения приведены дословно по тексту страницы; строки с Cooling power разделены по среде (Thermooil / Ethanol) и температуре.

Engineering Facts

14 facts · every claim linked to a page
Installation

The unit requires a 400 V three-phase supply with a 3x16 A fuse, so the electrical installation must be sized accordingly.

Determines the site power supply and protection device rating before installation.

Source
“Power supply requirement 400V 3~ 50Hz”
Installation

The cooling water supply must be between 5 °C and 20 °C and provide at least 1 bar differential pressure at the specified flow.

Cooling water conditions directly affect achievable cooling capacity and must be verified at the installation site.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

If cooling water temperature can fall below the dew point, the cooling water pipes inside the unit must be insulated to prevent condensation.

Prevents condensation damage and electrical risk in low-temperature cooling water installations.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides selection of cooling water quality and treatment to avoid corrosion or fouling.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation

Three-phase devices below 63 A are delivered with a cable but without a plug, so a suitable plug must be provided on site.

Affects electrical installation planning and the bill of materials for commissioning.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety

The unit has a leakage current above 3.5 mA, which must be considered for protective earthing and RCD selection.

High leakage current affects earth connection requirements and residual current device choice.

Source
“Attention: leakage current > 3,5mA”
Cumplimiento

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.

Defines acceptable site power quality and prevents invalid supply combinations.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Operation

The unit is rated for ambient temperatures from 5 °C to 40 °C, so the installation room must stay within this range.

Ambient temperature outside this range can impair performance and reliability.

Source
“max. ambient temperature 40 °C”
Performance

Cooling capacity depends on cooling water temperature; higher cooling water temperature reduces cooling power and may require higher flow.

Needed to correctly size the cooling water supply and predict process performance.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The pump connection is M30x1.5 male and the cooling water connection is G1/2 male, so matching hoses and adapters are required.

Ensures correct selection of hoses and fittings before installation.

Source
“Pump connection M30x1,5 male”
Installation

The minimum filling capacity is 5.1 l and the expansion tank holds 18 l, which determines the heat transfer fluid charge.

Needed to prepare the correct amount of heat transfer fluid for commissioning.

Source
“min. filling capacity 5,1 l”
Safety

The refrigerant is R-452A with GWP 2141 and a CO2 equivalent of 3.1 t, which is relevant for refrigerant reporting and handling.

Affects environmental compliance and refrigerant leak reporting obligations.

Source
“Global Warming Potential (GWP) 2141”
Selection

The unit is water-cooled and CFC/HCFC-free, so a cooling water supply is mandatory and no air-cooled option is implied.

Confirms that cooling water infrastructure is required for this model.

Source
“Refrigeration machine water-cooled, CFC- and HCFC-free”
Operation

The pump delivers 82 l/min maximum and 3 bar maximum pressure, with reduced flow at higher pressure, which matters for pressure-drop sizing.

Used to check whether the pump can overcome the pressure drop of the external circuit.

Source
“max. delivery 82 l/min”