Minichiller 1200 OLÉ Technical Data

Sommaire

  1. Overview p. 1
    Cover page identifying the Minichiller 1200 OLÉ model
  2. Spec p. 2
    Technical data per DIN 12876 in tabular form
  3. p. 2 table, 5 rows

Technical data according to DIN 12876

ParameterValue
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S618925

Engineering Facts

12 facts · every claim linked to a page
Selection

The unit is rated for an operating temperature range of -20 to 40 °C, with a permissible return-line temperature up to 80 °C, so it can serve applications requiring higher return temperatures.

Defines the process temperature window and the special 80 °C return-line allowance when selecting the chiller.

Source
“Operating temperature range -20...40 (80)*** °C”
Safety

The refrigerant is R-1270 (A3, H220), a flammable natural refrigerant, so the installation location must be assessed for A3 refrigerant safety requirements.

A3 flammability classification affects room ventilation, ignition-source control, and local refrigerant regulations.

Source
“Refrigerant (ASHRAE, GHS) R-1270 (A3, H220)”
Installation

The unit requires a 208-240 V single- or two-phase 50/60 Hz supply with a maximum current of 5 A and a 16 A fuse, so the electrical supply and protection must be sized accordingly.

Determines the site power connection, cable, and upstream fuse rating before installation.

Source
“Power supply requirement 208-240V 1~/2~ 50/60Hz”
Installation

Voltage and frequency tolerances are ±5% and ±2% respectively, but the combination of -5% voltage with +2% frequency is explicitly not allowed, so supply quality must be checked.

Prevents installation on a supply whose combined voltage/frequency deviation exceeds the permitted envelope.

Source
“-5% voltage and +2% frequency -> not allowed!”
Installation

The pump connection is M16x1 male and the included accessories are hose connector NW12, sleeve nuts M16x1, blank plug, and expansion-vessel cover, so mating hoses and fittings must match these threads.

Ensures correct hydraulic connection hardware is ordered and the circuit is plumbed without adapters.

Source
“hose connector NW12 #6087, sleeve nuts thread M16x1#6089, blank plug #6088, cover expansion vessel #25178”
Operation

The plastic pump is not resistant to acetone or polyglycols, so these fluids must be avoided or a more resistant plastic pump must be specified.

Prevents chemical attack and pump failure when selecting the heat-transfer fluid.

Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation

For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water, so the coolant must be prepared accordingly.

Avoids freezing and damage in the cooling circuit during low-temperature operation.

Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Performance

Cooling capacity is specified at 20 °C room temperature and may drop if ambient temperature rises, so capacity margins must account for the actual site ambient.

Prevents undersizing the chiller when installed in a warm room.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation

The unit is rated IP20 and must be operated between 5 °C and 40 °C ambient, so it must be installed in a dry, protected location within that ambient range.

Restricts installation to indoor, non-wet environments and defines the ambient temperature envelope.

Source
“Degree of Protection IP20”
Conformité

The equipment is EMC-classified as Class A, Group 1 to EN55011, so it is intended for industrial environments and may require additional measures in residential areas.

Affects site EMC planning and whether the installation is suitable for non-industrial locations.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

Single- and two-phase devices are delivered with a power cable and country-specific plug, so the country-specific plug must be specified at ordering.

Ensures the correct mains plug is supplied and avoids rework at commissioning.

Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”
Operation

Whisper mode reduces sound pressure to 51 dB(A) ±4 dB(A) but also reduces pump delivery to 14 l/min at 0.2 bar, so quiet operation trades off hydraulic performance.

Allows the engineer to judge whether noise reduction is compatible with the required flow and pressure.

Source
“Reduced sound pressure level: 51 dB(A): +/- 4 dB(A)”