Unichiller 020Tw-H Datasheet

Sommaire

  1. Overview p. 1
    Product introduction and main features of the chiller
  2. Spec pp. 1-2
    Technical data, performance and operating parameters
  3. Spec p. 2
    DIN 12876 compliant technical specifications table
  4. p. 2 table, 10 rows
  5. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
Net weight141 kg
sound pressure level +/- 4 dB(A)60 dB(A)
Power supply requirement230V 1~ 50Hz
max. current16 A
Fuse16 A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S338338

Technical data according to DIN 12876 — Unichiller 020Tw-H (Order-No.: 3024.0054.01)

CharacteristicValue
Operating temperature range-20...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power2 kW
Cooling power at 15°C2 kW
Cooling power at 0°C2 kW
Cooling power at -10°C1,5 kW
Cooling power at -20°C0,8 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity0,4 kg
CO2 equivalent0,6 t
Circulation pumpB
max. delivery25 l/min
max. delivery pressure3 bar
Delivery at 0,33 bar22 l/min
Delivery at 0,5 bar20 l/min
Delivery at 1,0 bar17 l/min
Delivery at 2,0 bar10 l/min
Delivery at 3,0 bar5 l/min
Pump connectionG3/4 male
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 0°C90 l/h
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity2,5 l
Volume of expansion4 l
Overall dimensions WxDxH **400x440x1230 mm

** — сноска к габаритам (Overall dimensions WxDxH **) в тексте страницы не раскрыта.

Engineering Facts

11 facts · every claim linked to a page
Installation

The chiller is water-cooled and requires a cooling water supply with a minimum differential pressure of 1 bar and a maximum pressure of 6 bar.

To ensure the cooling water circuit can deliver adequate flow and withstand the pressure without damage.

Source
“min. cooling water differential pressure 1 bar”
Installation

The unit is designed for cooling water intake temperatures between 5°C and 20°C, and pipes must be insulated if the water temperature falls below the condensation point.

Operating outside this range can reduce cooling capacity or cause condensation and damage.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power drops as cooling water temperature rises, and the required cooling water flow rate may increase.

To properly size the cooling water supply and predict performance under actual site conditions.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water may be used.

To avoid corrosion or damage by selecting compatible water quality and treatment.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Conformité

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and certain combinations (e.g., -5% voltage with +2% frequency) are not allowed.

To ensure the power supply meets the allowed tolerances and avoid invalid combinations that could damage the unit.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation

Single/two-phase devices are supplied with a power cable and country-specific plug, which must be specified when ordering.

To ensure the correct plug type is supplied for the installation site.

Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”
Safety

The refrigerant R-449A has a Global Warming Potential of 1397 and a CO2 equivalent of 0.6 t, which must be considered for environmental compliance.

To assess environmental impact and comply with refrigerant regulations.

Source
“Global Warming Potential (GWP) 1397”
Operation

The unit has a maximum ambient temperature of 40°C and a minimum of 5°C, limiting the installation location.

To ensure the chiller operates within its specified ambient conditions and maintains performance.

Source
“max. ambient temperature 40 °C”
Installation

The pump connection is G3/4 male and the cooling water connection is G1/2 male, requiring matching fittings.

To prepare correct mating connectors and hoses for installation.

Source
“Pump connection G3/4 male”
Maintenance

The minimum filling capacity is 2.5 l and the expansion volume is 4 l, which must be respected when filling the system.

To avoid insufficient filling or overflow during operation.

Source
“min. filling capacity 2,5 l”
Conformité

The equipment is classified as Class A, Group 1 for electromagnetic disturbance according to EN55011.

To ensure electromagnetic compatibility with other equipment in the installation environment.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”