Unichiller 300T Datasheet

Sommaire

  1. Overview p. 1
    Product introduction and main features of Unichiller 300T
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 1 table, 34 rows

Technical data according to DIN 12876 — Unichiller 300T (Order-No.: 3029.0043.01)

ParameterValue
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
Temperature stability at -10°C0,5 K
Safety classificationI / NFL
Cooling power at 15°C30 kW
Cooling power at 0°C18 kW
Cooling power at -10°C11 kW
Cooling power at -20°C6 kW
Refrigeration machineair-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Circulation pump:D3
max. delivery210 l/min
max. delivery pressure4,7 bar
Delivery at 1,1 bar202 l/min
Delivery at 1,5 bar193 l/min
Delivery at 2,0 bar179 l/min
Delivery at 2,5 bar159 l/min
Delivery at 3,0 bar140 l/min
Delivery at 3,5 bar115 l/min
Delivery at 4,0 bar77 l/min
Delivery at 4,5 bar31 l/min
Pump connectionG1 1/4 male
min. filling capacity14 l
Volume of expansion39 l
Overall dimensions WxDxH **905x2172x1900 mm
Power supply (3 Phase)400V 3~ 50Hz
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C

** см. сноску в оригинале (Overall dimensions WxDxH **)

Engineering Facts

14 facts · every claim linked to a page
Selection

The chiller is rated for an operating temperature range of -20 to 40 °C, so the process must stay within these limits.

Defines the usable process temperature window and excludes applications outside it.

Source
“Operating temperature range -20...40 °C”
Performance

Cooling capacity drops from 30 kW at 15 °C to 6 kW at -20 °C, so sizing must be based on the actual operating temperature.

Prevents undersizing when the process runs at low temperatures.

Source
“at 15°C 30 kW at 0°C 18 kW at -10°C 11 kW at -20°C 6 kW”
Installation

The unit requires a 400 V three-phase 50 Hz supply, so the site must provide a suitable three-phase feed.

Determines electrical infrastructure and whether a plug or hard wiring is needed.

Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation

Three-phase devices below 63 A are delivered with cable but without a plug, so the customer must provide the final connection.

Affects electrical installation planning and who supplies the plug/connection.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

The unit is IP20, so it must be installed in a dry indoor location protected from water and dust ingress.

Restricts installation environment and enclosure requirements.

Source
“Degree of Protection IP20”
Installation

Ambient temperature must stay between 5 and 40 °C, so the room ventilation and climate must be checked.

Out-of-range ambient conditions can impair operation and cooling performance.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Performance

Cooling capacity is valid at 20 °C room temperature and may drop at higher ambient temperatures, so derating must be considered.

Prevents overestimating available cooling in warm plant rooms.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation

The unit is air-cooled and needs space for airflow, so the stated space requirements must be respected.

Insufficient clearance reduces cooling performance and can cause overheating.

Source
“Please respect space requirements. See operating conditions at www.huber-online.com”
Installation

The pump connection is G1 1/4 male, so mating hoses and fittings must match this thread.

Ensures correct hydraulic connection and avoids adapters or leaks.

Source
“Pump connection G1 1/4 male”
Selection

The pump delivers 210 l/min at maximum and 202 l/min at 1.1 bar, so the external circuit pressure drop must be checked against the pump curve.

Confirms whether the pump can supply the required flow at the system's pressure drop.

Source
“max. delivery 210 l/min max. delivery pressure 4,7 bar Delivery at 1,1 bar 202 l/min”
Selection

Minimum filling capacity is 14 l and expansion volume is 39 l, so the loop volume and expansion must be planned accordingly.

Prevents underfilling and ensures adequate expansion volume for the application.

Source
“min. filling capacity 14 l Volume of expansion 39 l”
Safety

The refrigerant is R-449A with GHS classification H280 and GWP 1397, so refrigerant handling and environmental reporting requirements apply.

Affects safety procedures, leak detection and greenhouse-gas reporting obligations.

Source
“Refrigerant (ASHRAE, GHS) R-449A (A1, H280) Global Warming Potential (GWP) 1397”
Conformité

The equipment is EMC Class A Group 1, so it may cause radio interference in residential areas and is intended for industrial environments.

Determines suitability for industrial versus residential installation and EMC precautions.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and some combinations are not allowed, so supply quality must be verified.

Poor supply quality can cause malfunction or damage and must be checked before installation.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”