Unichiller 025Tw-H Technical Data Sheet

Sommaire

  1. Overview p. 1
    Product name and cover page of the datasheet
  2. Spec p. 2
    Technical data according to DIN 12876 in table form
  3. p. 2 table, 7 rows

Technical data according to DIN 12876

ParameterValue
max. current15 A
Fuse16 A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S622473

Engineering Facts

14 facts · every claim linked to a page
Installation

The chiller requires cooling water inlet temperature between 5°C and 20°C, so the facility water supply must be capable of staying within this window.

Determines whether the site cooling water can be used directly or needs a mixing/booster loop.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

If cooling water is colder than the condensation point, the cooling water pipes inside the unit must be insulated to prevent condensation.

Prevents condensation, corrosion and electrical risk when using cold facility water.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Cooling capacity is rated at 20°C room temperature, 15°C cooling water inlet and 1 bar differential pressure, so actual capacity will differ if site conditions deviate.

Needed to correctly compare quoted cooling power against real site conditions.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Performance

Higher cooling water temperature reduces cooling power and may require a higher cooling water flow rate.

Affects sizing of the cooling water supply and expected process performance.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and material compatibility to avoid corrosion and fouling.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Conformité

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.

Ensures the electrical supply stays within the unit's permissible operating envelope.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation

Single/two-phase devices are supplied with a power cable and country-specific plug, which must be specified at ordering.

Prevents delivery of the wrong plug type and avoids site rework.

Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”
Installation

Three-phase devices below 63 A are delivered with cable but without plug, so the site must provide a suitable connection.

Affects electrical installation planning and responsibility for the final connection.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Conformité

The equipment is classified as EN55011 Class A Group 1, which has implications for electromagnetic compatibility in residential environments.

Class A equipment may require additional EMC measures in residential or light-industrial locations.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Operation

The unit is IP20, so it must be installed in a dry location protected from water ingress.

Restricts installation location and enclosure requirements.

Source
“Degree of Protection IP20”
Operation

Ambient temperature must remain between 5°C and 40°C for safe and reliable operation.

Defines the allowable room conditions at the installation site.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Safety

The refrigerant R-449A is classified A1 with GHS hazard H280, so refrigerant handling and ventilation requirements apply.

Needed for risk assessment and compliance with refrigerant regulations.

Source
“R-449A (A1, H280)”
Selection

The unit has a CO2 equivalent of 0.7 t based on 0.5 kg of R-449A with GWP 1397, which matters for refrigerant leak reporting thresholds.

Determines whether periodic leak checks or F-gas record keeping are required.

Source
“CO2 equivalent 0,7 t”
Installation

Minimum cooling water differential pressure is 1 bar and maximum cooling water pressure is 6 bar, defining the required supply pressure range.

Ensures the facility water supply matches the unit's pressure requirements.

Source
“min. cooling water differential pressure 1 bar max. cooling water pressure 6 bar”