Selection
The chiller is rated for an operating temperature range of -20 to 40 °C, so the process must stay within these limits.
Defines the application window and excludes processes requiring lower or higher temperatures.
Source
“Operating temperature range
-20...40 °C”
Selection
Cooling capacity drops sharply at low temperatures, from 5.5 kW at 15 °C to only 0.2 kW at -20 °C.
Sizing must be based on the actual operating temperature, not the nominal maximum.
Source
“at 15°C
5,5 kW
at 0°C
2,3 kW
at -10°C
0,8 kW
at -20°C
0,2 kW”
Safety
The refrigerant is R-290 (propane, A3, H220), a flammable natural refrigerant, which affects installation and safety planning.
Flammable refrigerant requires attention to ventilation, ignition sources and local regulations.
Source
“Refrigerant (ASHRAE, GHS)
R-290 (A3, H220)”
Installation
The unit requires a 400 V three-phase supply with a 16 A fuse and draws up to 7 A.
Determines the electrical supply, cabling and protection needed at the installation site.
Source
“Power supply (3 Phase)
400V 3~ 50Hz
max. current
7 A
Fuse
16 A”
Installation
Three-phase devices below 63 A are delivered with a cable but without a plug, so a suitable plug must be provided on site.
Prevents delays at commissioning because the customer must supply and fit the plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
The unit is IP20 and must be installed in an environment between 5 °C and 40 °C ambient temperature.
IP20 offers no water protection and the ambient limits constrain the installation location.
Source
“Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Performance
Cooling capacity is specified at 20 °C room temperature and may drop if the ambient temperature rises.
Sizing must account for the real ambient conditions at the installation site.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
Voltage and frequency tolerances are ±5 % and ±2 % respectively, but not simultaneously in opposite directions.
Defines the acceptable power quality and the limits for generator or weak-grid operation.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Conformité
The equipment is EMC class A, group 1, which is intended for industrial environments.
Class A equipment may cause interference in residential areas and is intended for industrial use.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation
The pump connection is G1 1/4 male, and a matching hose coupling is included.
Determines the hose or piping adapters needed for the external circuit.
Source
“Pump connection
G1 1/4 male”
Operation
The minimum filling capacity is 5 l and the expansion volume is 7.5 l, which sets the heat transfer fluid charge.
Ensures the external loop is filled correctly and the expansion tank can absorb volume changes.
Source
“min. filling capacity
5 l
Volume of expansion
7,5 l”
Selection
The unit is intended for externally closed applications, which constrains the hydraulic circuit design.
Prevents use in open or pressure-less circuits that the design does not support.
Source
“For externally closed applications.”
Maintenance
The warranty is 4 years but requires registration.
Registration must be completed to secure the extended warranty coverage.
Source
“4-year warranty - registration required.”