Selection
The chiller is rated for an operating temperature range of -20 to 40 °C, which defines the process window it can support.
Confirms whether the unit can cover the required process temperatures before selection.
Source
“Operating temperature range -20...40 °C”
Performance
Cooling capacity drops from 18 kW at 0 °C to 6 kW at -20 °C, so low-temperature duty needs a larger unit or derating check.
Prevents undersizing when the process runs at the cold end of the range.
Source
“at -20°C 6 kW”
Installation
The unit requires a 400 V three-phase 50 Hz supply with a maximum current of 23 A.
Determines electrical supply, cable sizing and breaker selection at the installation site.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation
Three-phase devices below 63 A are delivered with cable but without a plug, so the site must provide a suitable connection.
Avoids delays at commissioning because no plug is included in the delivery.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances must be met simultaneously, and a -5% voltage with +2% frequency combination is not allowed.
Protects the compressor and electronics from supply conditions outside the permitted envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Operation
Cooling capacity is valid at 20 °C room temperature and may fall if ambient temperature rises.
Requires ventilation and ambient control in the plant room to preserve rated performance.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
The unit is rated IP20 and must be installed where ambient temperature stays between 5 and 40 °C.
Defines the acceptable plant-room environment and protection against dust and water.
Source
“min. ambient temperature 5 °C”
Safety
The refrigerant is R-449A with GHS classification H280 and a GWP of 1397, so leak detection and refrigerant handling rules apply.
Affects site safety classification, refrigerant inventory reporting and service procedures.
Source
“R-449A (A1, H280)”
Conformité
The equipment is EMC class A group 1, which is intended for industrial environments and may cause interference in residential areas.
Guides EMC planning and restricts installation to industrial or suitably filtered locations.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation
The pump connection is G1 1/4 male, so mating hoses and fittings must match this thread.
Ensures correct hydraulic connection hardware is ordered before delivery.
Source
“Pump connection G1 1/4 male”
Selection
The minimum filling capacity is 14 l and the expansion volume is 39 l, which sets the minimum loop volume and expansion allowance.
Prevents underfilled or overpressurised external circuits during design.
Source
“min. filling capacity 14 l”
Installation
The overall dimensions are 905 x 1582 x 1900 mm and the net weight is 533 kg, so floor space and lifting equipment must be planned.
Determines access route, floor loading and rigging requirements for installation.
Source
“905x1582x1900 mm”
Maintenance
The refrigerant charge is 5.75 kg with a CO2 equivalent of 8.0 t, which triggers periodic leak checks under F-gas rules.
Defines the legal leak-check frequency and service record obligations.
Source
“CO2 equivalent 8,0 t”