Unichiller 350Tw-H Technical Datasheet

Sommaire

  1. Overview p. 1
    Product introduction and general description of the chiller unit
  2. Spec pp. 1-2
    Technical data, performance figures and operating parameters per DIN 12876
  3. p. 2 table, 11 rows
  4. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
Volume of expansion22 l
Overall dimensions WxDxH **760x800x1615 mm
Net weight387 kg
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)19,5 A
Fuse (3 phase)3x20A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S621010

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unichiller 350Tw-H (Order-No.: 3021.0012.01)

ParameterValue
Operating temperature range-20...100 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,2 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationIII / FL
Heating power2 kW
Cooling power at 15°C35 kW
Cooling power at 0°C25 kW
Cooling power at -10°C16 kW
Cooling power at -20°C10 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity3 kg
CO2 equivalent4,2 t
Circulation pumpD3
max. delivery210 l/min
max. delivery pressure4,7 bar
Delivery at 1,1 bar202 l/min
Delivery at 1,5 bar193 l/min
Delivery at 2,0 bar179 l/min
Delivery at 2,5 bar159 l/min
Delivery at 3,0 bar140 l/min
Delivery at 3,5 bar115 l/min
Delivery at 4,0 bar77 l/min
Delivery at 4,5 bar31 l/min
Pump connectionG1 1/4 male
Cooling water connectionG3/4 male
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity15 l

Таблица приведена как напечатано (характеристика — значение); строки Cooling power и Delivery являются отдельными строками с указанием условий.

Engineering Facts

12 facts · every claim linked to a page
Installation

The chiller is water-cooled and requires a cooling water supply with a minimum differential pressure of 1 bar and a maximum pressure of 6 bar.

To size the cooling water circuit and ensure adequate flow and pressure for heat rejection.

Source
“min. cooling water differential pressure 1 bar”
Installation

The unit must be operated with cooling water intake temperature between 5°C and 20°C, and pipes must be insulated if below the condensation point.

To avoid condensation and ensure specified cooling performance; outside this range performance drops.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Cooling power is rated at 35 kW at 15°C, 25 kW at 0°C, 16 kW at -10°C, and 10 kW at -20°C, valid for 20°C room and 15°C cooling water.

To select the chiller for the actual heat load at the required process temperature.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Installation

The unit requires a 3-phase 400V 50Hz supply with max current 19.5 A and 3x20A fuses; three-phase devices under 63A are supplied with cable but without plug.

To plan electrical supply, protection, and provide a suitable plug on site.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Voltage and frequency tolerances are ±5% and ±2% respectively, but simultaneous opposite-sign deviations are not allowed.

To ensure the power quality at the installation site meets the unit's requirements.

Source
“-5% voltage and +2% frequency -> not allowed!”
Safety

The refrigerant R-449A has a GHS classification H280 (pressurized gas) and a GWP of 1397 with 3 kg charge (4.2 t CO2 equivalent).

To assess refrigerant safety, environmental impact, and leak detection requirements.

Source
“R-449A (A1, H280)”
Operation

The pump delivers 210 l/min max at 4.7 bar; flow drops with pressure, e.g., 140 l/min at 3.0 bar and 77 l/min at 4.0 bar.

To verify the pump can overcome the external circuit pressure drop at the required flow.

Source
“max. delivery 210 l/min”
Installation

The unit has IP20 protection and must be installed in an environment between 5°C and 40°C ambient temperature.

To ensure the installation location meets environmental and electrical safety requirements.

Source
“Degree of Protection IP20”
Maintenance

The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE, and EPDM, so suitable water quality is required.

To avoid corrosion and fouling by using compatible cooling water.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation

The unit requires a minimum filling capacity of 15 l and has a 22 l expansion volume.

To size the external circuit and ensure sufficient thermal fluid volume.

Source
“min. filling capacity 15 l”
Conformité

The equipment is classified as Class A, Group 1 for electromagnetic disturbance per EN55011.

To assess EMC compatibility and potential need for filtering or separation from sensitive equipment.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Selection

The unit is for externally closed applications and has an atmospheric open expansion tank.

To ensure the chiller is suitable for the intended closed-loop process.

Source
“For externally closed applications.”