The chiller is rated for an operating temperature range of -20 to 40 °C, so process requirements outside this window cannot be met.
Defines the application envelope and excludes processes needing lower or higher temperatures.
Source
“Operating temperature range
-20...40 °C”
Performance
Cooling capacity drops from 1.5 kW at 15 °C to 0.3 kW at -20 °C, so the required heat load must be checked at the actual operating temperature.
Sizing on nominal capacity alone will undersize the unit at low temperatures.
Source
“at 15°C
1,5 kW
at 0°C
1 kW
at -10°C
0,7 kW
at -20°C
0,3 kW”
Performance
Cooling capacity is valid at 20 °C room temperature and may drop as ambient temperature rises, so installation room conditions affect performance.
Ventilation and ambient conditions in the installation room must be planned for.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
The unit requires a 220-240 V single-phase 50 Hz supply with 8.5 A max current and a 16 A fuse.
Determines electrical supply, cabling and protection device sizing at the installation site.
Source
“Power supply requirement
220-240V 1~ 50Hz
max. current
8,5 A
Fuse
16 A”
Installation
Voltage and frequency tolerances are ±5% and ±2% but must not be combined in the unfavorable direction, so supply quality must be verified.
Prevents installation on unstable or out-of-tolerance power networks.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
The refrigerant is R-290 (A3, H220), a flammable natural refrigerant, so ignition sources and ventilation in the installation area must be considered.
Affects site safety assessment, ventilation and hazardous-area restrictions.
Source
“Refrigerant (ASHRAE, GHS)
R-290 (A3, H220)”
Operation
The plastic pump is not resistant to acetone or polyglycols, so these media must not be used as heat transfer fluid.
Prevents chemical attack and premature pump failure when selecting the heat transfer fluid.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.
Guides correct heat transfer fluid preparation for sub-zero operation.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation
The pump connection is G3/4 male, so mating hoses and fittings must match this thread.
Ensures correct hydraulic connection hardware is ordered and installed.
Source
“Pump connection
G3/4 male”
Performance
Pump delivery falls from 21 l/min at 0.5 bar to 6 l/min at 2.0 bar, so system pressure drop directly limits available flow.
The external circuit pressure drop must be matched to the pump curve during selection.
Source
“at 0,5 bar
21 l/min
at 1,0 bar
17 l/min
at 1,5 bar
11 l/min
at 2,0 bar
6 l/min”
Installation
The unit has IP20 protection, so it must be installed in a dry indoor location protected from water and dust ingress.
Restricts installation environment and enclosure requirements.
Source
“Degree of Protection
IP20”
Installation
Ambient temperature at the installation site must stay between 5 °C and 40 °C.
Defines allowable room conditions and rules out outdoor or extreme environments.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Maintenance
Minimum filling capacity is 3.8 l and the expansion tank is 1.7 l, so the external loop volume and fluid charge must be planned accordingly.
Prevents underfilling and ensures expansion volume is adequate for the loop.
Source
“min. filling capacity
3,8 l
expansion tank
1,7 l”
Conformité
The equipment is classified Class A, Group 1 for electromagnetic disturbance, which has implications for the electromagnetic environment at the installation site.
Class A equipment may require EMC measures in residential or sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”