Introduces the Unichiller P025-H chiller unit and its main features
Specpp. 1-2
Performance, temperature, and dimensional data according to DIN 12876
p. 2table, 10 rows
p. 1table, 31 rows
Technical data according to DIN 12876
Parameter
Value
Net weight
81 kg
sound pressure level +/- 4 dB(A)
64 dB(A)
Power supply requirement
220-240V 1~ 50Hz
max. current
15 A
Fuse
16 A
Pressure equipment category
Art. 4.3 PED
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S597891
Technical data according to DIN 12876 — Unichiller P025-H (Order-No.: 3052.0047.01)
Parameter
Value
Operating temperature range
-10...100 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,2 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
III / FL
Heating power at 240V
2,1 kW
Heating power at 230V
2 kW
Heating power at 220V
1,8 kW
Cooling power at ambient temperature +20°C
at 15°C
2,5 kW
at 0°C
2 kW
at -10°C
1,2 kW
Refrigeration machine
air-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-290 (A3, H220)
Global Warming Potential (GWP)
0,02
Refrigerant quantity
0,25 kg
CO2 equivalent
0,0 t
UN-number
UN 3358
Circulation pump:
B
max. delivery
25 l/min
max. delivery pressure
2,5 bar
Delivery at 0,5 bar
21 l/min
Delivery at 1,0 bar
17 l/min
Delivery at 1,5 bar
11 l/min
Delivery at 2,0 bar
6 l/min
Pump connection
G3/4 male
min. filling capacity
3,8 l
Volume of expansion
1,7 l
Overall dimensions WxDxH **
460x590x743 mm
** Overall dimensions WxDxH — см. сноску в оригинале; строка 'Cooling power at ambient temperature +20°C' напечатана без значения (значения приведены для 15°C, 0°C, -10°C).
Engineering Facts
14 facts · every claim linked to a page
Selection
The chiller uses R-290 (propane, A3 flammable) refrigerant, so the installation location must be assessed for flammable-refrigerant requirements.
A3 flammability classification affects room ventilation, ignition-source control and local safety compliance at the installation site.
Source
“Refrigerant (ASHRAE, GHS) R-290 (A3, H220)”
Selection
Cooling capacity is only 1.2 kW at -10 °C versus 2.5 kW at +15 °C, so the load must be checked at the actual working temperature.
Sizing on the +15 °C figure would overspecify the achievable duty at low temperature and risk insufficient cooling.
Source
“at -10°C 1,2 kW”
Performance
Cooling capacity figures are valid only at 20 °C room temperature and may drop at higher ambient temperatures.
The machine room temperature must be kept within the stated ambient range or the rated capacity cannot be relied on.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
The unit requires a 220-240 V single-phase 50 Hz supply with a 16 A fuse and draws up to 15 A.
The electrical supply, cable and protective device must be sized for 15 A on a dedicated single-phase circuit.
Source
“Power supply requirement 220-240V 1~ 50Hz max. current 15 A Fuse 16 A”
Installation
Voltage and frequency tolerances must be met simultaneously, and a -5% voltage with +2% frequency combination is explicitly not allowed.
Supply quality at the site must be verified against the combined tolerance rule before commissioning.
Source
“-5% voltage and +2% frequency -> not allowed!”
Operation
The plastic pump is not resistant to acetone or polyglycols, so these media must not be used as heat transfer fluid.
Fluid selection must avoid these media or a more resistant pump option must be ordered at extra cost.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.
The heat transfer fluid must be specified with antifreeze to operate safely down to -10 °C.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation
The pump connections are G3/4 male, and hose couplings for G3/4 male are included in the scope of delivery.
External piping and hoses must be ordered to match the G3/4 male thread.
Source
“Pump connection G3/4 male”
Performance
Pump delivery falls from 25 l/min at zero head to 6 l/min at 2.0 bar, so the system pressure drop determines the usable flow.
The external circuit pressure drop must be checked against the pump curve to confirm adequate flow.
Source
“Delivery at 2,0 bar 6 l/min”
Installation
The minimum filling capacity is 3.8 l with 1.7 l expansion volume, which sets the minimum fluid charge and expansion allowance.
The fluid volume and expansion vessel capacity must be planned for the external loop.
Source
“min. filling capacity 3,8 l”
Installation
The unit is rated IP20, so it must be installed in a dry, protected location free from water ingress.
IP20 limits the installation environment and rules out washdown or wet areas.
Source
“Degree of Protection IP20”
Installation
The permitted ambient temperature range is 5 °C to 40 °C, which constrains the room where the chiller is placed.
The installation room must stay within this range for reliable operation and rated performance.
Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Safety
The unit has adjustable overtemperature protection according to DIN 12876 and safety classification III/FL.
The overtemperature cut-out must be set and verified during commissioning as part of the safety concept.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Conformité
The equipment is classified Class A, Group 1 for electromagnetic disturbance to EN55011.
Class A equipment is intended for industrial environments and may require EMC measures in residential or sensitive areas.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”