Product introduction and general description of the unit
Specp. 2
Technical data according to DIN 12876
p. 2table, 25 rows
p. 1table, 26 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
920 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
12 bar
min. filling capacity
8,2 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Net weight
466 kg
Power supply requirement
400V 3~ 50Hz
max. current
35 A
Fuse
3x40A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S552631
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-45...150 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
I / NFL
Heating power
12 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
21 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
17,5 kW
at -20°C
9,5 kW
at -30°C
5,5 kW
at -40°C
3 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Refrigerant quantity
2,9 kg
CO2 equivalent
6,2 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Engineering Facts
14 facts · every claim linked to a page
Selection
The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so it suits automotive temperature simulation and material testing rather than general lab use.
Confirms the intended heat transfer fluid and application envelope before specifying the unit.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling water supply must be between 5°C and 20°C, and pipes must be insulated if the water temperature can drop below the dew point.
Defines the facility cooling water requirements and condensation protection needed at installation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
Cooling water differential pressure must stay between 1 bar and 4 bar, with a maximum supply pressure of 6 bar.
Ensures the site cooling water loop can deliver adequate flow without overpressurizing the unit.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit requires a 400 V three-phase 50 Hz supply with a maximum current of 35 A and 3x40 A fusing.
Determines electrical supply, breaker sizing and cable planning for the installation.
Source
“Power supply requirement 400V 3~ 50Hz”
Installation
Three-phase devices below 63 A are delivered with a cable but without a plug, so the site must provide a suitable connection.
Avoids surprises at commissioning regarding the missing mains plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
Leakage current exceeds 3.5 mA, which affects residual current device selection and earthing requirements.
Must be considered when specifying RCDs and protective earthing for the installation.
Source
“Attention: leakage current > 3,5mA”
Operation
The unit is rated IP20 and must be operated between 5°C and 40°C ambient, so it needs a clean, temperature-controlled indoor location.
Restricts installation environment and prevents operation in wet or dusty areas.
Source
“Degree of Protection IP20”
Performance
Cooling capacity falls from 21 kW at 20°C to 3 kW at -40°C, so low-temperature duty must be sized against the actual operating point.
Prevents oversizing assumptions based on nominal capacity when running cold.
Source
“at -40°C 3 kW”
Performance
Cooling capacity data are valid only at 20°C room temperature, 15°C cooling water inlet and 1 bar differential pressure.
Defines the reference conditions against which quoted capacities must be corrected for the site.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -outlet.”
Operation
The pump delivers 201 l/min at zero head but only 42 l/min at 5 bar, so system pressure drop directly limits achievable flow.
Needed to match the external circuit pressure drop to the available pump curve.
Source
“max. delivery 201 l/min”
Operation
Maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s, which limits how cold or viscous the fluid may be.
Constrains fluid selection and the lowest practical operating temperature.
Source
“max. permissible kin. viscosity 200 mm²/s”
Installation
The unit needs at least 8.2 l filling capacity and has a 19.9 l expansion tank, so the external loop volume must be planned accordingly.
Determines minimum fluid charge and expansion volume for the external circuit.
Source
“min. filling capacity 8,2 l”
Conformité
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Must be checked against the site power quality before commissioning.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Conformité
The unit is EMC Class A Group 1, so it is intended for industrial environments and may cause interference in residential areas.
Affects installation location and EMC planning in mixed-use facilities.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”